beautypg.com

Troubleshooting guide – U-Line CO29FF User Manual

Page 15

background image

CO29FF

15

Troubleshooting Guide

DANGER

ELECTROCUTION HAZARD
Never attempt to repair or perform maintenance on
the unit until the main electrical power has been
disconnected.

Troubleshooting - What to check when problems occur:

PROBLEM

POSSIBLE CAUSE

REMEDY

Unit not cold enough

Door gasket not sealing properly

Adjust door (See MAINTENANCE; DOOR ALIGN, ADJUST,
REVERSE).

Item(s) interfering with door

Reposition or remove item(s).

Dirty condenser coils

Clean condenser (See MAINTENANCE; CONDENSER
CLEANING).

Airflow to front grille blocked

Airflow must not be obstructed to front grille (See
OPERATION).

Temperature not set cold enough

Set control knob to cooler setting (See OPERATION).
Allow 24 hours for temperature to stabilize.

Water is leaking out the back of the
unit.

Water supply connection leaking

Tighten fitting as required.

Ice cubes sticking together

Door gasket not sealing properly

Adjust door (See MAINTENANCE; DOOR ALIGN, ADJUST,
REVERSE).

Infrequent use of cubes

Break apart cubes.

Noise during operation

Copper water supply tubing
contacting internal components

Carefully bend tubing away from cabinet and
components.

Certain sounds are normal.

Soft sounds from the fan and water/dropping sounds
from the ice maker will be heard.

No ice

Bin arm locked in upright position

Lower bin arm.

No water to unit

Turn on water or contact plumber.

Not enough ice

Ice cube size too large

Set cube size smaller (See MAINTENANCE; ICE MAKER;
ICE CUBE THICKNESS ADJUST).

Dirty condenser coils

Clean condenser (See MAINTENANCE; CONDENSER
CLEANING).

Water leaks into ice bucket.

Water level set too high

Set cube size smaller (See MAINTENANCE; ICE MAKER;
ICE CUBE THICKNESS ADJUST).

Fresh food section on Combo units
too cold

Ice bucket not fully inserted

Push ice bucket into place.

Freezer door not closed correctly

Be sure freezer door is closed correctly.

Unit too cold

Temperature control set too cold

Set control to warmer setting (See OPERATION).

ULIN_016357_30099.fm Page 15 Monday, March 27, 2006 10:22 AM