Caution – Tradewins Furniture RNC20 User Manual
Page 19
19
Damper Defrost
The damper defrost HRV has an electronically controlled
damper defrost mechanism. The defrost timer is activated
when the outside temperature drops below 27°F (-3°C). A
motor driven damper door mechanism closes off the sup-
ply air from ouside allowing the exhaust air to recirculate
through the unit. After the defrost period, the damper oper-
ates in the opposite direction to reopen the fresh air port.
Defrost cycle repeats until the temperature again rises
above 27°F (-3°C).
Defrost Operation
Dehumidistat Operation (HRV only)
The optional HRV remote controls include a dehumidistat
which controls humidity levels during the heating season.
The control has a selector knob with set points ranging
from 20% to 80% relative humidity (RH). Most people are
comfortable when indoor relative humidity levels are in a
range from 30 to 45%.
The dehumidistat switches the ventilator to high speed
when the moisture level in the building exceeds the
desired setpoint. The dehumidistat switches the HRV back
to low speed ventilation when the humidity has been
reduced below the setpoint. The dehumidistat should
only be used during the heating season. It must be set
to OFF position throughout the rest of the year.
Lengthening the run time may result in ice
buildup on the core.
CAUTION
Defrost Cycle DIP Switch Settings
Defrost DIP Switch Settings (located on the circuit board)
can be adjusted to increase the unit’s run (ventilation)
time. The three minute defrost time cannot change.
HS
REMOTE
DFR2
DFR3
ON
SW1
*Lengthening the run time may result in ice build-up on the core.
HS
REMOTE
DFR2
DFR3
ON
SW1
HS
REMOTE
DFR2
DFR3
ON
SW1
OFF
ON
OFF
ON
Factory Setting
3 minute defrost time
17 minute run time
Option 1*
3 minute defrost time
25 minute run time
Option 2*
3 minute defrost time
30 minute run time