Tripp Lite IS1800HG User Manual
Page 2

Rugged all-metal unit housing; ships ready for upright tower placement in any industrial, medical, office or network environment
Specifications
OVERVIEW
Amp Capacity
15A at 120V AC
Efficiency
96%
Form Factor
Small tower format
Input Plug Type
NEMA 5-20P-HG
Leakage Current
Less than 100 microamps
Let-through Voltage
(Combination Wave)
L-N: 250V L-G: 250V N-G: 0.5V
Let-through Voltage (Ring
Wave)
L-N: 20V L-G: 20V N-G: 0.5V
Noise Suppression Rating
35-65 DB
Nominal Voltage / Frequency
120V / 60Hz
Output Receptacle Qty / Type
6 NEMA 5-20R-HG
Over Current Protection
1x thermal, 2 pole, 10 amp
Shipping Weight
58.00 lbs. / 26.31 kg
Suppression Joule Rating
1190 (1020 input / 170 output)
Surge Test Conditions
Per ANSI/IEEE C62.41 - IEEE587 Cat. A & B test waveforms
Total Harmonic Distortion
Less than 1%
Transformer Type
Hospital Grade, low impedance transformer-based line isolation transformer
Unit Dimensions (HWD/in.)
7.75 x 8.25 x 12.25
VA / Watt Capacity
1800
INPUT
Input cord length (ft.)
10
Input cord length (m)
3.05
PHYSICAL
Cooling method
Convection
Unit Dimensions (HWD/cm)
19.69 x 20.96 x 31.11
CERTIFICATIONS
Certifications
Tested to UL60601-1
WARRANTY
Product Warranty Period
(Worldwide)
2-year limited warranty