Troubleshooting, Technical specification -- continued, Troubleshooting -- continued – Transition Networks Substation-Rated Industrial Ethernet SUBTF10XX-1XX-MX User Manual
Page 13

24
SIBTF10xx-1xx-Mx
24-Hour Technical Support: 1-800-260-1312 International: 00-1-952-941-7600
Standard
Description
Compliance Level
Remarks
IEEE1613, Power Substation Testing -- Continued
IEEE1613, Clause 7.3.2
Class 2 transverse mode
Class 1 common mode
Surge fast transient
waveform – power AC
Class 2 transverse mode
Class 1 common mode
Surge fast transient
waveform – power DC
Class 1 common mode
Surge fast transient
waveform – relay port
Class 1 common mode
Surge fast transient
waveform – Ethernet 10
Mbps
Class 1 common mode
Surge fast transient
waveform – Ethernet 100
Mbps
IEEE1613, Clause 8
Class 2
Radio frequency
susceptibility
IEEE1613, Clause 9
Class 1
ESD contact discharge 8kV
EMC Type Tests -- Continued
Technical Specification -- continued
Troubleshooting
If the industrial switch fails, isolate and correct the failure by determining the answers
to the following questions and then taking the indicated action:
1.
Is the “PRI” (primary power) LED illuminated?
NO
•
Ensure the power source is the proper voltage (48–170 VDC or 90–125
VAC, 50/60Hz).
•
Ensure that the positive, negative, and ground wires from the power
source are properly connected to the primary inputs.
•
Contact Technical Support:
US/Canada: 1-800-260-1312,
International: 00-1-952-941-7600.
YES
•
Proceed to step 2.
2.
(SIBTF10xx10x-MR models only) is the “AUX” (auxiliary power) LED
illuminated?
NO
•
If the device does not have an auxiliary power source, proceed to step 3.
•
Ensure the power source is the proper voltage (48–170 VDC or 90–125
VAC, 50/60Hz).
•
Ensure that the positive, negative, and ground wires from the power
source are properly connected to the auxiliary inputs.
•
Contact Technical Support: US/Canada: 1-800-260-1312, International:
00-1-952-941-7600.
YES
•
Proceed to step 3.
[email protected] -- Click the “Transition Now” link for a live Web chat.
25
Troubleshooting -- continued
3.
Is the “FAULT” LED illuminated?
NO
•
Proceed to step 4.
YES
•
Contact Technical Support: US/Canada: 1-800-260-1312, International:
00-1-952-941-7600.
4.
For each port with a cable installed is either the “10MB” or the “100MB” LED
illuminated?
YES
•
Proceed to step 5.
NO
•
For each port with a cable installed and its LED is OFF, check the cable
for proper connection.
•
For the fiber ports, verify that the TX and RX cables on the SIBTF10xx-
10x are connected to the RX and TX ports, respectively, on the device at
the other end of the fiber cables.
•
Contact Technical Support: US/Canada: 1-800-260-1312, International:
00-1-952-941-7600
5.
For each RJ-45 port with a cable installed (ports 1, 2, 3, and 4), check to see if
the 10MB or 100MB LED is illuminated.
•
10MB is ON = The industrial switch has selected 10Mb/s operation.
•
100MB is ON = The industrial switch has selected 100Mb/s operation.
•
If the speed is not correct, disconnect and reconnect the cable to restart the
initialization process.
•
Proceed to step 6.
6.
For each fiber port with a cable installed, is the “FD” (full-duplex) LED
illuminated?
NO
•
The industrial switch has selected half-duplex mode.
•
If the mode is not correct, disconnect and reconnect cable to restart the
initialization process.
•
Check the cable for proper connection.
•
Contact Tech Support: 1-800-260-1312, Int’l: 00-1-952-941-7600.
YES
•
The industrial switch has selected full-duplex mode.
•
If the mode is not correct, disconnect and reconnect cable to restart the
initialization process.
•
Check the cable for proper connection.
•
Contact Tech Support: 1-800-260-1312, Int’l: 00-1-952-941-7600.