Setup of external static pressure

Matching with the resistance (External static pressure)
of the duct to be connected, be sure to set up the tap
exchange according to the basic operation procedure

(

1

2

3

4

5

6

).

• For the item code in Procedure

3

, specify [5d].

• For the set data in Procedure

4

, select the setup

data of static pressure outside of the machine to be
set up from the table below.

(Exchange by wired remote controller)

*1: For SM1401BT, set 65Pa.
*2: For SM1401BT, set 90Pa.

To incorporate a filter sold separately

When mounting a filter sold separately, be sure to set
up the tap exchange according to the type of filter.

In this case, also follow to the basic operation
procedure (

1

2

3

4

5

6

).

• For the item code in Procedure

3

, specify [5d].

• For the set data in Procedure

4

, select the setup

data of filter to be incorporated from the table below.

• Select with shifting of the short plug on the

indoor unit microcomputer P.C. board.

Set data

0000

0001

0003

0006

External static pressure

40Pa

70Pa *1

100Pa *2

20Pa

Standard (At shipment)

High static pressure 1

High static pressure 2

Low static pressure

Set data

0000

0001

Filter sold separately

Standard filter (At shipment)

Optical regeneration deodorizing filter

High-performance filter 65, 90

Deodorant filter Ammonia deodorizing filter

Short plug position

External static

pressure

40Pa

Standard
(At shipment)

70Pa

High static-
pressure 1

100Pa

High static-
pressure 2

20Pa

Low static-
pressure

Filter sold separately

Standard filter
(At shipment)

Optical regeneration
deodorizing filter

*1
High-performance filter 65
High-performance filter 90
Deodorant filter
Ammonia deodorizing filter

——

——

*1 Resistance of high-performance filter 65 and 90,

deodorant filter, or ammonia deodorizing filter is
equivalent to 30Pa. Therefore, set the resistance
(external static pressure) of a duct to be connected
to 40Pa.

• Short plug position

(CN112, CN111, CN110 from the left)