46-649 Jupiter Magnetostrictive Transmitter - F
OUNDATION
fieldbus™
5.2
Agency Approvals
FM & CSA
2X1-XXXXXXX-XXX
Intrinsically Safe
Class
I, Div. 1:
2X2-XXXXXXX-XXX
Groups A, B, C, & D
2X3-XXXXXXX-XXX
Class
II, Div. 1:
2X4-XXXXXXX-XXX
Groups E, F, & G
Class
III, IP66 TYPE 4X, T4
FISCO
2XX-XXXXXXX-XXX
Explosion Proof
➀
Class
I, Div. 1
Groups B, C, & D
Class
II, Div. 1
Groups E, F, & G
Class
III, IP66 Type 4X T5 at 80° C
2XX-XXXXXXX-XXX
Non-Incendive
Class
I, Div. 2
Groups A, B, C, & D
Class
II, Div. 2
Groups E, F, & G
➁
Class
III, IP66 Type 4X T5 at 80° C
ATEX
2XA-XXXXXXX-XXX
Flame Proof
II 1/2 G EExd IIC T6
2XB-XXXXXXX-XXX
2XC-XXXXXXX-XXX
2XD-XXXXXXX-XXX
2XE-XXXXXXX-XXX
Intrinsically Safe
➂
II 1 G EEx ia IIC T4
2XF-XXXXXXX-XXX
FISCO
2XG-XXXXXXX-XXX
2XH-XXXXXXX-XXX
AGENCY
MODEL
PROTECTION METHOD
AREA CLASSIFICATION
➀
M20 conduit connections not CSA approved explosion proof
➁
FM approval Class II, Div. 2 Groups F & G only
➂
Materials marked as category 1 equipment and used in hazardous areas requiring this category, shall be installed in such a way that, even in
the event of rare incidents, the aluminum enclosure cannot be an ignition source due to impact or friction
5.2.1 Agency Specifications –
Explosion Proof Installation
Factory Sealed: This product has been approved by Factory
Mutual Research (FM) and Canadian Standards Association
(CSA) as a Factory Sealed device.
NOTE: Factory Sealed: No Explosion Proof conduit fitting (EY seal) is
required within 18" of the transmitter. However, an Explosion
Proof conduit fitting (EY seal) is required between the haz-
ardous and safe areas.
Caution: Grounding (+) will cause faulty operation, but will not
cause permanent damage.
5.2.2 Agency specifications ATEX Intrinsically safe
Entity parameters Fieldbus Fisco:
Ui = 17.5V Ii=380mA Pi = 5.32W Ci = 0.705 nF Li = 3µH