High efficiency, Wiring diagrams, Specifications – Sylvania QUICKTRONIC POWERSENSE T8 User Manual
Page 4: System life / warranty, Control information, Powersense

Catalog #
Date
Type
Project
Prepared by
Comments
SPECIFICATION DATA
Output Wiring: Lamp wiring for dimming ballasts can differ significantly from non-dimming ballasts and from
other manufacturers dimming ballasts. Take care to connect lamp lead wires as shown on the applicable
ballast diagram.
Lamp Seasoning: For optimal performance, fluorescent lamps may require seasoning for up to 12 hours prior to low temperature starting &
low level dimming. Refer to NEMA LSD 23-2002 Lighting Systems Division: Recommended Practice — Lamp Seasoning for Fluorescent Dimming Systems
Wiring Diagrams
Black
White
Black
White
Violet (+)
Grey (-)
Violet (+)
Grey (-)
Red
Red
Red
Red
Blue
Blue
Blue
Blue
LAMP
1
Yel/Blk
Yellow
Yellow
LAMP 1
LAMP 1
ELECTRONIC
BALLAST
ELECTRONIC
BALLAST
LAMP 2
BALLAST
ELECTRONIC
LAMP 1
LAMP 4
LAMP 3
LAMP 2
Yellow/Black
Yellow
Yellow
Red/Black
Red/White
Red
Red/White
Blue
Blue/White
Blue/White
Blue/Black
Grey (-)
Black
White
Violet (+)
Black
White
Black
White
Violet (+)
Grey (-)
Violet (+)
Grey (-)
Red
Red
Red
Red
Blue
Blue
Blue
Blue
LAMP
1
Yel/Blk
Yellow
Yellow
LAMP 1
LAMP 1
ELECTRONIC
BALLAST
ELECTRONIC
BALLAST
LAMP 2
Yel/Blk
Yellow
Yellow
Red/Black
Red/White
Red
Red/White
Blue
LAMP 1
LAMP 3
ELECTRONIC
BALLAST
Black
White
Violet (+)
Grey (-)
LAMP 2
1 lamp
2 lamp
3 lamp
4 lamp
POWERSENSE
T8 DIM
Performance Guide
High Efficiency,
T8 Controllable Lighting Systems,
UNV (120-277V)
Input
Rated
Ballast
Input
System
1
Item
OSRAM SYLVANIA
Current Lamp
Lumens No. of Factor System
Mean
Power (W) Efficacy
Number Description
(AMPS) Type
(lm) Lamps (BF) Lumens Lumens 120V 277V (lm/W) BEF
2
50705
QTP 1x32T8/UNV DIM-TC
0.27/0.12 FO32XP
3000
1
0.88
2640
2480
30 30
88
2.93
0.05
150
140
8 8
0.24/0.11 FO30/SS
2850
1
0.88
2510
2360
28 28
90
3.14
0.05
145
135
8 8
0.22/0.10 FO28/SS
2725
1
0.88
2400
2255
25 25
96
3.52
0.05
135
130
8 8
0.20/0.09 FO25/SS
2475
1
0.88
2180
2045
23 23
95
3.83
0.05
125
115
7 7
50707
QTP 2x32T8/UNV DIM-TC
0.51/0.24 FO32XP
3000
2
0.88
5280
4965
59 57
93
1.54
0.05
300
280
14 14
0.48/0.20 FO30/SS
2850
2
0.88
5015
4715
55 53
95
1.66
0.05
285
270
14 14
0.43/0.18 FO28/SS
2725
2
0.88
4795
4510
51 49
98
1.80
0.05
275
255
13 13
0.39/0.16 FO25/SS
2475
2
0.88
4355
4095
45 44
99
2.00
0.05
250
235
13 13
50714
QTP 3x32T8/UNV DIM-TCL
0.73/0.30 FO32XP
3000
3
0.88
7920
7445
87 84
94
1.05
0.05
450
425
20 20
0.68/0.30 FO30/SS
2850
3
0.88
7525
7075
81 78
96
1.13
0.05
430
400
20 20
0.62/0.26 FO28/SS
2725
3
0.88
7195
6760
73 72
100
1.22
0.05
410
385
19 19
0.56/0.24 FO25/SS
2475
3
0.88
6535
6140
67 66
99
1.33
0.05
370
350
19 19
50716
QTP 4x32T8/UNV DIM-TCL
0.96/0.40 FO32XP
3000
4
0.88
10,560
9925
114 110
96
0.80
0.05
600
565
27 27
0.92/0.39 FO30/SS
2850
4
0.88
10,030
9430
107 104
96
0.85
0.05
570
535
26 26
0.82/0.35 FO28/SS
2725
4
0.88
9590
9015
98 95
101
0.93
0.05
545
510
25 25
0.74/0.32 FO25/SS
2475
4
0.88
8710
8190
91 89
98
0.99
0.05
495
465
24 24
Products are all 10-pack. *Striation might occur with SUPERSAVER lamps.
1: System Efficacy calculation based on lowest input power value.
2: Ballast Efficiency Factor (BEF) shown = (Ballast Factor x 100) divided by Input Power (Note: calculation based on lowest wattage value).
Starting Method: Programmed Rapid Start
Circuit Type: Series
Lamp Frequency: >40 kHz
Lamp CCF: Less than 1.7
Starting Temp: 50°F/10°C minimum
for OCTRON T8 lamps
Input Voltage: 120-277V, ±10%
Input Frequency: 50/60 Hz
THD: <10% @ Full Output
Power Factor: >98% @ Full Output
UL Listed Class P, Type 1 Outdoor
CSA or C/UL Certified
70°C Max Case Temperature
FCC 47CFR Part 18 Non-Consumer
Class A Sound Rating
RoHS compliant
3
ANSI C62.41 Cat. A Transient Protection
Remote mounting (Max. wire length from
ballast case to lampholder)
• up to 8ft for full wattage T8s
• no remote mounting for SUPERSAVER
3 Complies with European Union Restriction
of Hazardous Substances Directive (Directive
EC 2002/95)
Specifications
Data based on F32T8
Item Number
50707 QTP 2 x 32T8 / UNV DIM-TC
QUICKTRONIC
Number of Lamps (1, 2, 3, 4)
System Type - DIMMING/Case Size
Line Voltage (120-277V)
Primary Lamp Wattage
System Life / Warranty
QUICKTRONIC products are covered by the
QUICK 60+
®
warranty, a comprehensive
lamp and ballast system warranty. For
additional details, refer to the QUICK 60+
warranty bulletin.
Data based on SYLVANIA OCTRON
®
lamps
shown. QUICKTRONIC
®
POWERSENSE
ballasts are also compatible with other
manufacturers equivalent lamp types that
meet ANSI specifications, including F17,
F25, F32, U-Bend equivalent lamps and
SUPERSAVER lamps.
T8
POWERSENSE
®
High Efficiency
OSRAM SYLVANIA
National Customer
Service and Sales Center
1-800-LIGHTBULB
(1-800-544-4828)
www.sylvania.com
Control Information
QUICKTRONIC POWERSENSE ballasts are
compatible with a wide range of low voltage
(0-10VDC) and power line fluorescent controllers
available from various manufacturers.
Low Voltage Control Specs: Ballast will source
up to 0.5mA for 0-10VDC control purposes.
May be wired as a Class 1 or Class 2 circuit-
consult Local and National Electrical Codes.
Power Line Control Specs: Specification-
grade fluorescent controls are available
for 120V or 277V operation of controllable
analog electronic fluorescent ballasts.
Controls must be suitably rated for both the
type (e.g. Fluorescent Phasecontrol) and size
(e.g. 600W) of the connected load.
SYLVANIA, the system solution, QUICK60+, POWERSENSE, See the World in a New Light, PROStart, OCTRON and SUPERSAVER are registered trademarks of OSRAM SYLVANIA Inc.
ELOGIC is a trademark of OSRAM SYLVANIA Inc. QUICKTRONIC is a registered trademark of OSRAM AG. NEMA Premium is a registered trademark of National Electrical Manufacturers Association.
©2011
OSRAM
SYL
VANIA
Specifications subject to change without notice.