OMEGA FP-5060 Series Micro Flow Sensor
4. Fitting
Installation
CAUTION:
• Maximum pipe fi tting torque: 10 ft - lbs (13 N m).
• DO NOT overtighten. Failure to observe torque specifi cation may permanently damage sensor ports.
5. Calibration
The K-Factors listed below represent the number of pulses the sensor will generate for each engineering unit of fl uid which passes.
They are listed in U.S. gallons, liters and mL by sensor model:
Technical Notes:
•
Compatible fi ttings (customer supplied): Female union (shown), reducer, or hose barb type.
•
Always apply thread sealant to sensor port threads to prevent leakage.
Sealant
FP-5060
Pipe fitting
Pipe
Pipe fitting
Pipe
3. Surface
Mount
Instructions
1
Mounting surface
2
Remove sensor then use correct
screws for panel material.
Mounting surface (top),
68 mm (2.68 in.) bolt circle
120°
#6 or M3 metric
screws recommended
Mounting surface (side)
Sensor
Model
PULSES PER
U.S. GAL
PULSES PER
LITER
PULSES PER
mL
FP-5061
9950
2629
2.629
FP-5062
9950
2629
2.629
FP-5063
3160
834.9
0.835
FP-5064
3160
834.9
0.835