Omega Speaker Systems DRX-TC User Manual
Page 15

Note 1:
Bit 2&3 set the speed of process totalize. The time it would take process totalize to
reach the non-totalize reading is shown in the following table:
Bit 3
Bit 2
Time to reach regular reading
0
0
1 minute
0
1
1 hour
1
0
1 day
1
1
30 day
3. DECIMAL POINT :
This is one byte (2 characters) as:
value
meaning
1
XXXXXX.
2 XXXXX.X
3
XXXX.XX
4
XXX.XXX
5
XX.XXXX
6
X.XXXXX
Note 1:
For TC and RTD models, value must be 1 to 3 only.
4. FILTER TIME CONSTANT:
This is one byte (2 characters) as:
value
meaning (per no. of readings)
0
No filtering
1
2
2
4
3
8
4
16
5
32
6
64
7
128
Page 11