Installation, Australia only, Important – Regency F2402M User Manual
Page 7
Regency Freestanding Woodstove
7
AUSTRALIA ONLY
MINIMUM CLEARANCE TO
COMBUSTIBLE MATERIALS
Please read the section below carefully as clearances depend on whether the airmate or the
rear heat defl ector is installed on the stove.
Measurements "From Unit" are from the top plate of the stove to a side wall or to a corner,
and from the rear heat shield to a back wall.
Residential Installation Clearances to Combustible Walls
Unit
From Unit From Corner From Flue Center-Line
A
B
C D
E
F
Medium F2402M
with Airmate* 450mm 125mm 150mm 755mm 290mm 445mm
with Rear Defl ector* 450mm 150mm 225mm 755mm 315mm 555mm
*Airmate fi tted, and 900mm long half round enamelled mild steel fl ue shield or half perforated decromesh
fl ue shield fi tted
*Rear fi rebox shield extension fi tted, and full length half perforated decromesh fl ue surround or 900mm
long half round enamelled mild steel fl ue shield fi tted.
Flue systems tested:
Acorn
Special
Insulated
FLOMET Super Single
Shamic
1A
Floor Protector:
6mm thick fi bre cement sheet with thermal conductivity 0.41 W/m degree K underneath heater extending 300mm
in front and 200 mm from the sides of the fi rebox opening.
Use only the instructions and clearance dimensions on this page for
heaters to be installed in Australia.
The Regency F2402M has been tested by the AHHA Testing Laboratory
and conforms to AS/NZS 2918:200, Report No. ATL19-04.
AUSTRALIA ONLY
The Regency F2402M has been tested with the fl ue kits listed
below. A default fl ue kit as listed in AS/NZS 2918:2001 may also
be used.
These are the only fl ue kits certifi ed for use with this heater for
installation in Australia.
INSTALLATION
IMPORTANT