F37 Regency

®

Rear Flued Room Sealed Freestanding Gas Heater

System Data - F37

Burner Inlet Orifi ce Sizes:
NG LPG
Burner

#37

#52


Max. Input Rating

31.7 mj

Min. Input Rating

16 mj


Supply Pressure
NG

min.

1.13kPa

LPG

min.

2.75kPa

Manifold Pressure
NG

.89

kPa

LPG

2.55

kPa

GAS CONNECTION

The gas connection is a 1/2" NPT Male
Thread. Copper can be used or other con-
nections approved by AG 604.

When using copper or fl ex connectors use only
approved fi ttings. Always provide a union so
that gas lines can be easily disconnected for
burner and/or valve servicing. Flare nuts for
copper lines are usually considered to meet
this requirement.

Important: Always check for gas leaks with a
soap and water solution or gas leak detector.
Do not use open fl ame for leak testing.

Note: Prior to any pressure testing of

the gas supply piping system
that exceeds test pressures of
3.45 kPa, this appliance must
be disconnected from the pip-
ing system. If test pressures
equal to or less than 3.45 kPa
are used then this appliance
must be isolated from the piping
system by closing its individual
manual shut-off valve during the
testing.

VERTICAL TERMINATION WITH

CO-LINEAR FLEX SYSTEM

THE APPLIANCE MUST NOT BE CONNECTED TO A CHIMNEY FLUE SERVING

A SEPARATE SOLID FUEL BURNING APPLIANCE.

This appliance is designed to be attached to two 3" (76mm) co-linear aluminium fl ex running the
full length of the chimney. See the Flueing Arrangements chart in the "Flue Arrangement" sec-
tion for minimum and maximum fl ue lengths. See chart below for minimum distances from roof.
Periodically check that the fl ue is unrestricted.

Masonry chimneys may take various contours which the fl exible liner will accommodate. However,
keep the fl exible liner as straight as possible, avoid unnecessary bending.

The Air Intake pipe must be attached to the inlet air collar of the termination cap.

Required Parts:

Part #

Description

946-529

Co-linear DV Vertical Termination Cap

948-305

3" Flex - 35 ft.

640-994 F37

Dura-Vent

Adapter

946-563

Co-Axial to Co-Linear Adapter Kit

which contains the following:

Co-linear

Flex

Adapter

(270-585)

Outer

Pipe

(946-257)

Inner

Pipe

Adapter

(946-219)

Approved Caps
980 Vertical

Termination

Cap

923GK 3"

Co-linear

Adapter

with

ashing