beautypg.com

Roberts Gorden VANTAGE II CTH2-125 User Manual

Page 2

background image

Printed in U.S.A.

CTH2SNA

5M 0608 Rev H

VANTAGE® II

Model

CTH2-40

CTH2-60

CTH2-80

CTH2-100

CTH2-125

CTH2-150

CTH2-175

Minimum Length of Straight Tube*

[ft] A

10

20

20

30

40

50

60

Minimum Length of U-tube*

[ft, in] B

N/A

11.7

11.7

16.7

21.7

26.7

31.7

Overall Minimum Length of Straight Tube

[ft, in] C

11, 5.5

21, 5.5

21, 5.5

31, 5.5

41, 5.5

51, 5.5

61, 5.5

Overall Minimum Length of U-tube

[ft, in] D

N/A

13, 0.5

13, 0.5

18, 0.5

23, 0.5

28, 0.5

33, 0.5

Input (Btu/h) x (1000)

40

60

80

100

125

150

175

Inlet Pressure

[in wc] NG min.

4.6

4.6

4.6

4.6

4.6

4.6

5

LPG Propane min.

11

11

11

11

11

11

11

NG & LPG Propane max.

14

14

14

14

14

14

14

Gas Connection

NPT

½"

½"

½"

½"

½"

¾"

¾"

Weights

Overall Length of Tube and Accessory Packages [ft]

10

20

30

40

50

60

70

Hot Rolled or Aluminized Tube

with Aluminum Reflector

[lb]

52

86

120

161

206

240

281

Aluminized Tube with Stainless Steel Reflector

[lb]

66

113

152

208

265

304

360

Burner

[lb] 40

Aluminized U-tube with Aluminum End Caps

[lb] 19

Aluminized U-tube with Stainless Steel End Caps

[lb] 20

Fuel

NG or LPG Propane

Electrical Supply

120 V, 60 Hz, 1 A (Run) 5 A (Start)

Heat Exchanger Tubing

10 ft Sections, 4" dia, 16 Gauge, First 10 ft ALUMI-THERM® Steel Tubing
[Remaining Hot Rolled, Heat Treated Aluminized or Double Porcelain Coated Steel Tubing]

Exhaust Flue

dia 4"

Reflector and End Caps

.024 Aluminum [Optional - .024 Stainless Steel Type 304]

Control System

Honeywell® SmartValve® II Combines Gas Valve and Hot Surface Electronic Ignition Control

Fully Automatic, Four-Try, 100% Shut-Off, Prepurge, Auto Reset, LED Indicator Status

Approved As

Indoor (Vented or Unvented)

Certification

ANSI Z83.20/CSA 2.34, 2.17

Warranty

Three-Year Limited (Refer to Installation, Operation and Service Manual for Details)

**Clearances B, C and D can be reduced by 50% for locations 25 ft (7 m) or more downstream of the burner. For other mounting options and associated clearances, complete

installation, operation and service criteria, please see the current issue of the Installation, Operation and Service Manual.

Clearances to Combustibles **[in]

Model

CTH2-40

CTH2-60

CTH2-80

CTH2-100

CTH2-125

CTH2-150

CTH2-175

Horizontal 45°

Horiz.

45°

Horiz.

45°

Horiz.

45°

Horiz.

45°

Horiz.

45°

Horiz.

45°

Horiz.

45°

A

6

8

6

8

6

8

6

10

6

10

6

12

8

12

B

27

8

35

8

38

8

40

8

46

8

50

8

52

8

C

53

51

63

60

66

66

71

74

77

78

80

84

82

85

D

27

46

35

54

38

60

40

64

46

69

50

74

52

79

������������������������

���������

��������������������������

�����

�������

������������������

�����

�������

����

�������

���������������

���������

��������

������������������

��������������������������

���

��������

*For additional lengths, please see the current Installation, Operation and Service Manual.

© 2008 Roberts-Gordon LLC All rights reserved. No part of this work covered by the copyrights herein may be reproduced or copied in any form or by any means – graphic, electronic, or mechanical, including photocopying,

recording, taping, or information storage and retrieval systems – without written permission of Roberts-Gordon, LLC.

Roberts-Gordon LLC

1250 William Street

P.O. Box 44

Buffalo, NY 14240-0044 USA

Telephone: 716.852.4400

Fax: 716.852.0854

Toll Free: 800.828.7450
www.rg-inc.com

European Office:

Roberts-Gordon Europe Limited

Telephone: +44 (0)121 506 7700

Fax: +44 (0)121 506 7701

Installation Code and Annual Inspections:

All installations and service of ROBERTS GORDON® equipment must be performed by a contractor qualified in the installation and service of equipment sold and supplied by Roberts-Gordon

and conform to all requirements set forth in the ROBERTS GORDON® manuals and all applicable governmental authorities pertaining to the installation, service and operation of the equipment.

To help facilitate optimum performance and safety, Roberts-Gordon recommends that a qualified contractor annually inspect your ROBERTS GORDON® equipment and perform service where

necessary, using only replacement parts sold and supplied by Roberts-Gordon.

Further Information:

Applications, engineering and detailed guidance on systems design, installation and equipment performance is available through ROBERTS GORDON® representatives.

Please contact us for any further information you may require, including the Installation, Operation and Service Manual.

This product is not for residential use.

This document is intended to assist licensed professionals in the exercise of their professional judgment.

This manual is related to the following products: