PART 1 GENERAL

Provide gas-fired unit heaters, designed and manufactured for

indoor use.

1.1 SECTION INCLUDES

A. Unit Heater
B. Controls

1.2 REFERENCES

A. American National Standards Institute (ANSI) / Canadian

Standards Association (CSA): Establish requirements applicable

to construction, certification and installation of unit heaters.

a. Standard ANSI Z83.8 / CSA 2.6 “Gas Unit Heater and Gas-

Fired Duct Furnaces” (latest edition)

B. IAS: Establishes requirements applicable to construction and

certification of unit heaters.

a. Standard No.10-96 “Unit Heaters for Residential Use”

(latest edition)

C. National Fire Protection Association (NFPA): Establishes fire

prevention standards.

a. Article 54: National Fuel Gas Code (latest edition)

b. Article 70: National Electric Code (latest edition)

1.3 SUBMITTALS FOR REVIEW

A. Product Data: Provide data with dimensions, service

connections, accessories, controls, electrical nameplate data and

wiring diagrams.

1.4 PROJECT CLOSEOUT PROCEDURES

A. Training: Provide owner with verbal operating instructions as

well as original manufacturer’s installation, operation and service

manuals.

1.5 QUALITY ASSURANCE

A. Manufacturer Qualifications: Company specializing in

manufacturing the products specified in this section (gas-

fired unit heaters) with a minimum of ten years documented

experience. Equipment shall be the standard product of the

manufacturer and shall have complete catalogued data.

B. Installer Qualifications: All installation and service of unit

heaters must be performed by a contractor qualified in the

installation and service of said products with proof of a

minimum of three years documented experience.

C. Factory Testing: Each unit heater shall be factory tested. Testing

shall consist of verification of correct operation of burners,

manifold, control assembly and electrical components.

1.6 REGULATORY REQUIREMENTS

A. Conform to ANSI Z83.8 / CSA 2.6, latest edition, and provide

evidence that the unit heater and its control system have been

found in compliance with these standards by a nationally

recognized testing laboratory.

1.7 WARRANTY

A. The product shall have a manufacturer’s limited warranty of at

least 24 months, subject to the manufacturer’s standard warranty

limitations.

PART 2: PRODUCTS

2.1 MANUFACTURERS

A. COMBAT® by Roberts-Gordon UHA[X][S]-Series

2.2 MANUFACTURED UNITS

A. Unit: Gas-fired, power-vented unit heater with tubular heat

exchanger. Units shall have a minimum of 82% thermal

efficiency. The standard unit shall consist of a non-separated

combustion design with an aluminized heat exchanger. Design

and heat exchanger alternatives shall be offered as follows:

1. Separated Combustion: A separated combustion unit shall

consist of an enclosed sealed burner box to which

combustion air is vented through a piece of internal flexible

air duct. This duct terminates at an exterior cabinet flange to

which a vent run to the outside of the heated space should be

attached.

2. Stainless Steel Heat Exchanger: A stainless steel heat

exchanger unit shall consist of heat exchanger tubes, heat

exchanger tube supports, heat exchanger tube plates and a

vent box produced of 409 stainless steel.

2.3 FABRICATION

A. Casing and Components: Galvannealed steel panels, minimum

20 gauge. All panels shall be lined with a minimum of

3/8"(10mm) thick insulation.

B. Access Door: Door shall be provided for easy service of all

critical components.

C. Finish: Standard finish is a heavy-duty white powder-coat.

D. Louvers: The cabinet shall be equipped with horizontal louvers.

Louvers shall be spring-held and adjustable for directing airflow.

2.4 HEAT EXCHANGERS, BURNERS AND GAS TRAIN

A. Heat Exchangers: For Models 30-125, heat exchanger tubes

shall be of a six-pass design with 1.5" (38 mm) outer diameter

[aluminized steel] [409 stainless steel] tube. For Models 150-

400, heat exchanger tubes shall be of a four-pass design with

1.75" (44 mm) outer diameter [aluminized steel] [409 stainless

steel] tube. Heat exchangers shall not be clamshell design. For

Models 150-400, the heat exchanger tubes shall be dimpled to

provide efficient heat transfer. The tube plates shall be made of

[aluminized steel] [409 stainless steel]. The tube supports shall

be made of [galvannealed steel] [409 stainless steel].

B. Burners: The burners shall be in-shot type, directly firing each

heat exchanger tube individually. Burners shall be capable of

burning natural gas or LPG.

C. Gas Train: The gas train is constructed of black pipe and includes

a single-stage gas valve. The valve provides the regulator, main

gas and manual shutoff functions.