beautypg.com

Installation – Regency Wraps S2400M User Manual

Page 9

background image

Regency Freestanding Woodstove

9

Minimum Alcove Clearance to Combustible Materials

The Regency Freestanding models have been alcove approved and must be installed
with a listed double wall connector to the ceiling level.

Note: Minimum alcove ceiling height - 84"

Maximum depth of alcove - 36"

Floor Protection

A combustible fl oor must be protected by non-combustible
material (like tile, concrete board, or certifi ed to UL-1618 or
as defi ned by local codes) extending beneath the heater and
a minimum of 6" (152mm) from each side and minimum 16"
(406mm) from the front face of the stove and minimum 6"
(or the rear clearance to combustibles whichever is smaller)
from the rear of the stove.

When installed with horizontal venting, non-combustible fl oor
protection must beneath the fl ue pipe and extend 2" (51mm)
beyond each side.

Minimum Overall Width (X) of Floor
Protector
for all installations:

Stove

F2400M

36" (914 mm)

Step Stove

S2400M

36" (914 mm)

Minimum Overall Depth (Y) of Floor Protector

Residential Residential Mobile Home Alcove

Unit "C" Vent Close Clearance Close Clearance

Y Z

Y

Z

Y Z

Y

Z

Medium F2400M
with Airmate
46" (1168 mm) 6" (152 mm) 45"* (1143 mm) 5" (127 mm) 45" (1143 mm) 5" (127 mm) 45"* (1143) 5" (127 mm)
with Rear Defl ector 46" (1168 mm) 6" (152 mm) 45" (1143 mm) 5" (127 mm) 45" (1143 mm) 5" (127 mm) 45" (1143) 5" (127 mm)

Medium S2400M 46" (1168 mm) 6" (152 mm) 45"* (1143 mm) 5" (127 mm) 45" (1143 mm) 5" (127 mm) 45"* (1143) 5" (127 mm)
- Step Stove

*The rear clearance to combustibles is less than 6" (, for corner installations the rear corners may be angled to take advantage of the closer clear-
ances.

INSTALLATION

From From Flue Min. Min.Hearth

Unit

Unit

Center-line Width to Rear Wall

G H

I J K L

Medium F2400M

with Airmate 15" (381 mm) 5.5" (139 mm) 27" (685 mm) 12" (304 mm) 54" (1371 mm) 48" (1219 mm)

with Rear Defl ector 15" (381 mm) 6.5" (165 mm) 27" (685 mm) 13" (330 mm) 54" (1371 mm) 49" (1244 mm)

Medium S2400M Step Stove 15" (381 mm) 5.5" (139 mm) 27" (685 mm) 12" (304 mm) 54" (1371 mm) 48" (1219 mm)

NOTE: In Canada, fl oor protection must extend 18" (450mm) to the

front and 8" (200mm) to each side and back of the stove.

This manual is related to the following products: