CYCL = Cycle Timer allows a compressor to rest between cycles. Can be

set from 0 to 5 minutes in 1 minute increments.

WARNING:

A wrong short cycle setting can damage your

equipment. This should only be changed by a trained HVAC professional.

CAL = Calibration offset. Changes the displayed temperature from the

actual temperature by +3 to -3 degrees in one degree increments.

Increasing the offset by +2 will cause the thermostat to display a

temperature that is 2 degrees higher than the actual room

temperature.

Security Lockout to Protect the Settings

The buttons on the front of the thermostat can be locked with a password.

To create a password:

1. Press the

and

buttons at the same time and hold them in

for 5 seconds.

You will be asked for a 4 digit password.

2. Each digit is set using the

and

buttons. Press the

to

move to the next digit. Press

to move back.

3. The password is saved after 10 seconds or by pressing

and

at the same time.

All of the front buttons are now locked out until the password is entered.

Pressing any button will cause

to flash.

To unlock the buttons:

1. Push and hold the

and

buttons for 5 seconds until the

request for password is displayed.

2. Enter the digits for the password by pressing the

and

buttons. Press the

to move to the next digit. Press

to

move back.

!