beautypg.com

Overview, Specifications, Output specifications – RCI 10-175UL User Manual

Page 2: Stand-by specifications

background image

Overview

The 10-175UL is a power limited power supply/charger that will convert 115VAC / 60Hz
input, into two individually PTC protected 12VDC or 24VDC output, (see specifications).
They are intended for use in applications requiring UL Listing for Access Control (UL294)
and applications requiring an interface with Fire Alarm Control Panels. It must be installed
in accordance with National and Local Electrical Codes and Regulations.

Specifications

UL listed Access Control (UL294)

CSFM approved - California State Fire Marshal

MEA approved - NYC Dept. of Buildings 18-98-E

NFPA 101 (Life Safety)

Input 115VAC/60 Hz, .6 amps

Switch selectable 12VDC or 24VDC power limited output

1.75 amps continuous supply current @ 12VDC or 24VDC

Latching fire alarm tie-in with manual reset

Filtered and electronically regulated output

Charge current: 0.4 amps Max

Aux relay output: (form “C”, 1 amp, 28VDC)

AC Fail output relay (form “C” 1 amp, 28VDC)

Enclosure Dimensions: 15.5”H x 12”W x 4.5”D

Output Specifications

Output VDC Switch Position

Max. Stand-by

Max. Alarm

Battery

Load DC

Load DC

(Optional)

12VDC

SW1 Open

1.75 amps

1.75 amps

12VDC

24VDC

SW1 Open

1.75 amps

1.75amps

24VDC

Stand-By Specifications

Output

4Hr. of Stand-by & 5 minutes of alarm

12VDC / 7 AH Battery

Stand-by = 1.25 amps

24VDC / 7 AH Battery

Alarm = 1.25 amps