Catalog No.: 6000.29B
Effective: 7-15-08
Replaces: 1-1-08
MVB – Type P
Models 504-2004
Model
Shown without H-bypass or Cold Water Run options
Dimensions (in.)
MBTUH
B
D
E
F
G
H
K
M
N
P
R V
Model
Input
Output
Height
NPT
NPT
Flue Ø
C/A Ø
Ship
Weight
(Lbs.)
Foot-
(Ft
2
)
Amps*
P-504
500
420
43
30
35
23-3/4
1
2
8
14-1/8
6
36
8
2
600
5.4
12
P-754
750
630
49
36
41
29-3/4
1
2
10
16
6
42
8
2
660
5.4
12
P-1104
1100
935
55
43
47
35-3/4
1-1/4
2-1/2
10
16
6
49
8
2
720
5.4
12
P-1504
1500
1275
61
50
53
41-3/4
1-1/4
2-1/2
12
18-1/8
8
53
8
2
780
5.4
12
WHP-2004
1900
1615
75
61
65
53-3/4
2
2-1/2
14
20-1/8
8
69
9
5
940
5.4
18
- Ratings shown are for elevations up to 4,500 feet. For installations at elevations
above 4,500 feet, please consult the factory for additional instructions.
* Current draw is for heater only.
(Supply breaker must have delayed trip.)
RATES OF FLOW
20°F ∆
∆
∆
∆T
Minimum Flow
Maximum Flow
Model
GPM
∆
∆
∆
∆P (ft.)
GPM ∆
∆
∆
∆P (ft.) ∆
∆
∆
∆T (°F)
GPM
∆
∆
∆
∆P (ft.)
∆
∆
∆
∆T (°F)
P-504
N/A
N/A
65
5.5
13
100
11.3
9
P-754
65
6.4
65
6.4
20
100
13.8
13
P-1104
94
13.6
85
11.5
22
113
18.6
17
P-1504
N/A
N/A
102
18.7
25
113
22.2
23
WHP-2004
N/A
N/A
102
22.7
32
113
27.2
29
Raypak, Inc. 2151 Eastman Avenue, Oxnard, CA 93030 (805) 278-5300 Fax (800) 872-9725 www.raypak.com
CLEARANCES
Certified
Minimum
Recomm.
Service
Front
24”
24”
Rear
12”
24”
Right
1”
–
Left
1”
–
Top
0”
10”
Floor
0”
–
Vent
1”
–
PUMP
Pump
Model
Model
HP
Amps*
P-504
1611
¼
6
P-754
1630
½
7
P-1104
1630
½
7
P-1504
1634
1
14
WHP-2004
1636
1 ½
22
* Current draw is for pump only