beautypg.com

Battery replacement procedure – Rackmount Solutions PRO500iE User Manual

Page 15

background image

14

English

BATTERY REPLACEMENT PROCEDURE

PLEASE READ THE CAUTIONS AND WARNINGS BEFORE ATTEMPTING
TO REPLACE THE BATTERIES
Hot-swappable batteries mean that the batteries can be replaced without
powering down the whole UPS system.
NOTE: If there is a power interruption while replacing the hot-swappable

batteries, with the UPS on, the load will not be backed up. To
hot-swap the batteries start with step number 6.

1. Turn off the equipment that is plugged into the output receptacles of the
UPS.
2. Press and release the On/Off/Test button on the front panel to turn the UPS
OFF.
3. Unplug the UPS's AC power cord from the AC wall outlet.
4. Unplug the equipment from the output receptacles of the UPS.
5. Unplug the computer interface cable from the rear panel of the UPS.
6. Remove the retaining screws from the bottom of the front panel of the UPS.
7. Grasp the bottom of the front panel and gently pull the front panel off the
UPS.
8. Lay the front panel on top of the UPS.

PRO500E
PRO500iE

PRO700E
PRO700iE

PRO1100E
PRO1100iE

Battery

Model #

1-12V9Ah

2-12V7Ah

3-12V7Ah

PRO1500E
PRO1500iE

3-12V9Ah

PRO-E
Model #

Replace batteries with the same number and type as originally
installed in the UPS. These batteries have pressure operated vents.
These UPSs contain sealed non-spillable lead acid batteries.

CAUTION:

Panasonic
Part #

LC-R129

LC-R127

LC-R127

LC-R129

Yuasa Part # REW45-12

NP 7-12

NP 7-12

REW45-12

This manual is related to the following products: