Ppendix b, Pecifications – Rackmount Solutions 3000VA User Manual
Page 14

A
PPENDIX B
S
PECIFICATIONS
MODEL KIN-
600
AP/RM
KIN-
1000
AP/RM
KIN-
1200
AP/RM
KIN-
1500
AP/RM
KIN-
2200
AP/RM
KIN-
3000
AP/RM
( U P S
o u t l e t s )
600
VA/
360W
1000
VA/
600W
1200
VA/
720W
1500
VA/
900W
2200
VA/
1320W
3000
VA/
1800W
C a p a c i t y
( B y p a s s
o u t l e t s )
500VA 500VA 500VA 500VA
(220
~240V
only)
N/A N/A
Voltage
+/-25% at line input
INPUT
Frequency
50 or 60 Hz +/-10% (auto sensing)
Voltage (on
battery)
Simulated sine wave at 100V or
110V/115V/120Vor 220V/230V/240V +/- 5%
Frequency
(on battery)
50 or 60 Hz +/- 0.5%
Voltage
Regulation
(AVR)
AVR automatically increase output voltage
15% above input voltage if –9% to –25% of
nominal. AVR decrease output voltage 13%
below input voltage if +9% to +25% of
nominal
OUTPUT
Transfer Time
2/4 milliseconds, including detection time
EMI/RFI filter
10dB at 0.15MHz,50dB at 30MHz
P R O T E C T I O N
A n d
F I L T E R I N G
Overload
Protection
UPS automatic shutdown if overload
exceeds 110% of nominal at 60 seconds and
130% at 3 seconds
Unit Input
Circuit Breaker
For overload & Short circuit protection
10Base-T
Cable
Port
Network(UTP,RJ -45) compatible jacks
Short Circuit
UPS output cut off immediately or input fuse
protection
BATTERY
Type
Sealed, Maintenance-free lead acid
Typic al
Recharge Time
8 hours (to 90% of full capacity)
Protection
Automatic self-test & discharge protection,
Replace battery indicator
Back-up Time
3– 180 min (depending on computer load)
1 2