CERTIFIED TEST DATA

Air delivery and sound level ratings are certified by

the Home Ventilating Institute Division of AMCA, based
on testing performed by an independent third party testing
laboratory, in accordance with HVI standards. This NuTone
model is listed by Underwriters' Laboratories Inc.

The air delivery of a ventilating system may be
determined by:
1. Determine the equivalent duct length for each 90 degree

elbow by adding one foot of duct length for each inch of
duct diameter, i.e., a 4 inch diameter duct elbow equals
4 feet equivalent duct length and an 8 inch diameter
duct elbow equals 8 feet equivalent duct length.

2. Add the total straight length of duct and the equivalent

length for each elbow to obtain the total equivalent
duct length.

3. Locate the intersection of the fan performance curve and

the total equivalent duct length curves and draw a vertical
line down to the CFM scale and read the system air
performance.
(NOTE: 3

1

4

" x 10" duct equals 6 inch diameter duct.)

DIMENSIONS

16

1

/4"

14 5/8

"

17

1/8

"

5 5

/8

"

9 7

/8

"

7 7

/8"

0.45

AIR PERFORMANCE CURVE

(4 In. Duct to 10 Foot Lengths)

STATIC PRESSURE
INCHES OF WATER

CFM

0.05

76

73

71

68

66

64

62

60

57

54

0.1 0.15 0.2 0.25 0.3 0.35 0.4

0.5

100

50

0

0.00

0.10

0.20

0.30

0.40

0.50

ST

A

T

IC PRESSURE–INCHES OF W

A

TER

50 Feet

40 Feet

30 Feet

20 Feet

10 Feet

CFM CUBIC FEET PER MINUTE

75

125

25