Location

The cooker may be located in a kitchen, a kitchen/diner

or bedsitting room but not in a bathroom, shower room

or garage.

For information regarding the fitting of flexible supply

pipes, the highest temperature at the rear of this cooker

which may come into contact with the supply pipe is

70°C above ambient.

When the appliance has been installed there must be

enough space fot the hotplate lid (when present) to open

fully.

Positioning the Cooker

Caution:

Some soft or badly fitted floor coverings can be damaged

when the cooker is moved across their surface for

cleaning. It is advisable to ensure that the floor covering

in the area below the cooker is either securely fixed so as

not to ruck up when the cooker is moved or, if preferred,

removed.

Important Safety Requirements

This appliance must be installed in accordance with the

Gas Safety (Installation and Use) Regulations (current

addition) and the I.E.E. Wiring Regulations. Detailed

recommendations are contained in the following British

Standard Codes of Practice - B.S. 6172, B.S. 5440: Part

2 and B.S. 6891: Current Editions.

Provision for Ventilation

The room containing the cooker should have an air supply

in accordance with B.S. 5440: Part 2: Current Editions.

The following requirements for ventilation must be met.

The cooker should not be installed in a bed sitting room

with a volume of less than 20m

3

, if it is installed in a

room of volume less 5m

3

an air vent of effective area of

110cm

2

is required; if it is installed in a room of volume

between 5m

3

and 10m

3

, an air vent of effective area 50cm

2

is required, while if the volume exceeds 11m

3

no air vent

is required. However, if the room has a door which opens

directly to the outside, no air vent is required even when

the volume is between 5m

3

and 11m

3

.

If there are other fuel burning appliances in the same

room, B.S. 5440: Part. 2: Current Editions should be

consulted to determine the requisite air vent

requirements.