beautypg.com

Anchor clamp(s) installation, continued, Water connections – Pentair ThermalFlo User Manual

Page 15

background image

7

ThermalFlo Installation and User’s Guide

HEAT PUMP

ANCHOR CLAMP

AIR COIL GUARD

AIR

COIL

BOLT ANCHOR

(installer provided)

HEAT PUMP

BASE

1-3/8" HEX BOLT

(installer provided)

CONCRETE

EQUIPMENT PAD

Figure 5.

POOL HEATER

CHEMICAL LOOP

2 LB.

CHEMICAL RESISTANT

CHECK VALVE

CHEMICAL FEEDER

TO POOL OR SPA

POOL PUMP

FROM POOL OR SPA

MANUAL BYPASS VALVE

FILTER

Figure 6. Standard Plumbing Layout

Anchor Clamp(s) Installation, continued

6. Drill a hole in the cement using a masonry drill bit, with a

diameter as determined by the concrete anchor, at each of the
marks on the equipment pad. The hole should be approximately
1½ in. deep.

7. Insert a bolt anchor into each of the holes. Be sure the anchors

are set completely into the holes

8. Position the anchor clamps so that the holes in the clamps are

over the bolt anchors. Be sure that the clamp hooks are over the
lip of the heat pump base, see Figure 5.

9. Insert an anchor bolt through each clamp into the anchor and

tighten to secure the clamp and heat pump to the equipment pad.

Water Connections

Plumbing layout

See Figure 6, illustrating the standard plumbing layout with a single heat pump unit. Following the diagram from
right to left, the plumbing sequence is as follows:

Pool > Skimmer and Main Drain > Pool Pump > Filter > Heat Pump > Check Valve > Chemical Loop > Chlorinator > Pool

NOTE: For normal installations, do not install a shut-off valve or any kind of variable restriction in
the water piping between the heat pump outlet and the pool/spa.
The heat pump must be protected from back-siphoning of water. If there is any chance of back-siphoning,
provide a check valve between the pool and the heat

pump outlet. Arrangement of pool system components

other than as illustrated in Figure 6. and the following diagrams can affect the operation of the heat pump’s
water pressure switch. Location of the heat pump above or below the pool water surface can also affect
operation of the switch. In general, the pressure switch can be adjusted to accommodate this effect if the heat
pump water connections are no more than six (6) feet below the pool water surface or no more than fifteen 15
feet above it. See instructions for pressure switch adjustment (

page 20

) in the heat pump start-up section of this

manual for more information. If the heat pump is installed outside of this range, an external pressure switch may
need to be installed in the plumbing upstream of the heat pump. Call the Pentair Water Heat Pump Technical
Service department at (800) 831-7133 for details.
Be advised that when pool equipment is located below the pool surface a leak can result in large-scale water
loss or flooding. Pentair cannot be responsible for such water loss or flooding or the damage caused by either
occurrence.