beautypg.com

Panasonic 6296 User Manual

Page 2

background image

All technical features and data are subject to changes without notice, resulting from continuous development and improvement.

Product Leaflet

Date of issue

Revision / Date of revision

MEW00132 2001-10-19 9

/

2008-10-10

Type numbers

6295

Enclosed heat detector, 57

°C, class A2 S (54 to 70°C).

6296

Enclosed heat detector, 72

°C, class B S (69 to 85°C).

6297

Enclosed heat detector, 87

°C, class C S (84 to 100°C).

6298

Enclosed heat detector, 117

°C, class E S (114 to 130°C).

3390

Label holder (100 holders per packet, excl. labels).

3391

Labels for 3390 (10 sheets à 132 labels)

Detector mounting holes, 2x(4x7 mm) c/c = 70 mm. E+/E- = Ext. LED. A/B = zone line in/out
(or end-of-line device). Connectors for wire diameter 0.6 - 1.2 mm (approx. 0.3 - 1.13 mm

2

).

Connection box mounting holes, 2x(5 mm) c/c = 108 mm. The connection box is prepared for
required number of compression glands, one, two or three. A gland is approx. 30 mm high.

Technical data

Voltage (V DC)

rated
allowed
normal


24
12-30
24 (zone line voltage)

Current consumption at nom.
voltage, quiescent (mA)


0

Current limitation required, when
active (mA)

(EBL equipment has current limitation.)

6295-6297: Must be min. 6 and max. 40
6298: Must be min. 6 and max. 30

Ext. LED output
voltage (V)
current output (mA)


Zone line voltage minus 2 V
Max. 10 (no internal current limiter)

Alarm resistance (Ω)

For 6295-6297: approx. 400. For 6298: approx. 680

Internal capacitance (nF)
Internal inductance

For 6295-6296: max. 50
For 6295-6296: 0

Ambient temperature (

°C)

operating
(Min. / Typical / Max.)
storage

6295 (A2 S):

6296 (B S):

6297 (C S):

6298 (E S):

-40 /+25 /+50

-40 /+40 /+65

-40 /+55 /+80

-40 /+85 /+110

-45 to +70

-45 to +70

-45 to +70

-45 to +70

Ingress Protection rating

IP67 (attached conn. box, silicon gasket and compression glands required)

Static response temperature

57, 72, 87, or 117

°C depending on detector / class. See text.

Size

∅ x h (mm)

Detector: 95 x 42 Connection box: 100 x 35
Detector + Connection box: 100 x 75 (excl. compression glands)

Weight (g)

Detector: 82 Connection box (incl. 3 glands): 134

Construction


Colour

Body (6295, 6296): ABS
Body (6297, 6298): Modified Polycarbonate.
Protector (on the body) & Connection box: Modified Polycarbonate.
Grey (N8, Munsell colour code)

Approvals

05 EC Certificate no. 0845-CPD-232.1192 (6295); EN54-5
05 EC Certificate no. 0845-CPD-232.1193 (6296); EN54-5
05 EC Certificate no. 0845-CPD-232.1194 (6297); EN54-5

05 EC Certificate no. 0845-CPD-232.1195 (6298); EN54-5

ATEX classification (for 6295 &
6296 only)

6295:

II 3GD EEx nA II T5 (T100°C), -40°C ≤ T

a

≤ 50°C

6296:

II 3GD EEx nA II T5 (T100°C), -40°C ≤ T

a

≤ 65°C

This manual is related to the following products: