P2201 (22 KW)
P2701 (27 KW)
P3201 (32 KW)
Rated Wattage - (Standby)
@1.0 PF LPG *
22,000
27,000
32,000
Rated Wattage - (Standby)
@1.0 PF NG *
19,800
24,300
28,800
Voltage
120/240 volts
120/240 volts
120/240 volts
Rated Current
184/92 amps LPG
224/112 amps LPG
255/133 amps LPG
Frequency
60 HZ
60 HZ
60 HZ
Power Factor
1.0
1.0
1.0
Max. Ambient Temp Rise
105°C
105°C
105°C
Insulation class
H
H
H
Engine
GM 3.0 L
GM 3.0 L
GM 3.0 L
Engine Type
Water cooled inline (4 cyliners) Water cooled inline (4 cyliners) Water cooled inline (4 cyliners)
RPM
1800
1800
1800
Displacement cc (c.i.d)
2966 (181)
2966 (181)
2966 (181)
Bore X Stroke mm (inches)
101.60 x 91.44 (4.00 x 3.60)
101.60 x 91.44 (4.00 x 3.60)
101.60 x 91.44 (4.00 x 3.60)
Compression Ratio
10:5:1
10:5:1
10:5:1
Valve arrangement
Overhead valve
Overhead valve
Overhead valve
Governor
Electronic, Isochronous
Electronic, Isochronous
Electronic, Isochronous
Ignition system
Solid State Distributor
Solid State Distributor
Solid State Distributor
Starter
12vdc, Solenoid Shift
12vdc, Solenoid Shift
12vdc, Solenoid Shift
Alternator
12vdc
12vdc
12vdc
Oil Capacity (w/o filter)
4 qts (3.8L)
4 qts (3.8L)
4 qts (3.8L)
Oil Capacity (with filter)
5 qts (4.7L)
5 qts (4.7L)
5 qts (4.7L)
Oil Filter
PF-25 or equivalent
PF-25 or equivalent
PF-25 or equivalent
Radiator capacity
Shipped with 50/50 mix of
water and propylene glycol
antifreeze.
Shipped with 50/50 mix of
water and propylene glycol
antifreeze.
Shipped with 50/50 mix of
water and propylene glycol
antifreeze.
Spark plug
AC Delco R45TS
AC Delco R45TS
AC Delco R45TS
Battery
BCI Group 34, minimum
750 CCA
BCI Group 34, minimum
750 CCA
BCI Group 34, minimum 750
CCA
Air filter
019-0255
019-0255
019-0255
Minimum Content
Requirements for Natural Gas
(NG) **
1000 BTU’s per cubic foot
1000 BTU’sper cubic foot
1000 BTU’sper cubic foot
Minimum Content
Requirements for Liquid
Propane Vapor (LPG) **
2520 BTU’sper cubic foot
2520 BTU’sper cubic foot
2520 BTU’s per cubic foot
Consumption at Full Load for
Natural Gas (NG)
280 cubic feet per hour
304 cubic feet per hour
315 cubic feet per hour
Consumption at Full Load for
Liquid Propane Vapor (LPG)
3.44 gallons per hour
3.71 gallons per hour
3.99 gallons per hour
Dimensions (see next page
for installation drawing)
66”L x 35”W x 41”H
66”L x 35”W x 41”H
66”L x 35”W x 41”H
Shipping Weight
1300
1300
1300
Normal Operating Range
-20°F (-28.8°C) to 104°F (40°C)
* Note: Rated wattage is specified at sea level, 60°F ambient temperature, and propane fuel (with 2500 BTU/cuft). Rated wattage decreases
approximately 3.5% for each 1000ft above sea level and approximately 1% for each 10°F above 60°F ambient temperature.
** Fuel supply pressures must be between 4 oz (6” w.c.) and 6 oz (11” w.c.) at inlet to the unit.