All technical features and data are subject to changes without notice, resulting from continuous development and improvement.
Product Leaflet
Date of issue
Revision / Date of revision
MEW01047 2008-01-23
2
/
2008-09-18
Type numbers
4375
Heat detector, 60
°C, class A2 S.
4376
Heat detector, 80
°C, class B S.
In the detector:
See also "Engineering Instructions for detectors Type 435x".
A
Contact for base 2324
B
Contact for base 2324
The detector is plugged in a base 2324. End-of-line device depending on the zone line input.
Technical data
Voltage (V DC)
rated
allowed
normal
24
10-30
24 (zone line voltage)
Current consumption at nom. voltage,
quiescent (mA)
Max. 0.015
Current limitation required, when
active (mA)
(EBL equipment has current limitation.)
Must be min. 6 and max. 100
Ambient temperature (
°C)
operating (Min. / Typical / Max.)
storage
4375 (A2 S):
4376 (B S):
-10 /+25 /+40
-10 /+40 /+60
-25 to +70
-25 to +70
Static response temperature (
°C)
55 (4375) and 72 (4376)
Ingress Protection rating (estimated)
IP51
Size
∅ x h (mm)
102 x 39
Weight (g)
54
Construction / Colour
Modified Polycarbonate / Grey (N8, Munsell colour code)
Approvals
07 EC Certificate no. 0786-CPD-20334 (4375); EN54-5 + A1
07 EC Certificate no. 0786-CPD-20335 (4376); EN54-5 + A1
A
B
The zone line is connected to the base 2324 (A+ & B-)