beautypg.com

Sensor wiring – Pentair Water Chemistry Controller Smart pH User Manual

Page 8

background image

Smart pH

8

SENSOR WIRING

pH SENSOR

Open front panel by removing the top two screws completely and unscrewing the lower two screws about half

way. The front cover will now fold down like a shelf for easy access to the wiring connections and dipswitches.

Route the sensor wires through the small strain relief into the Smart pH and to the appropriate connectors

(green terminal bar) in the Smart pH (see Fig. 6).

The polarity (+ and -) of the pH sensor must be observed. The pH sensor wire (+) is clear, and the pH sensor

wire (-) is green. Leave excess wire outside the controller enclosure. Do not stuff excess wire inside the

controller as this may cause excess strain on sensor and relay connections. Do not cut the sensor wire. If the

cable is longer than needed, it should be coiled neatly and attached under the controller enclosure.

WARNING

Sensors are shipped with a protective cap covering the electrode tip to protect the sensing element. Sensors should be

kept in the protective cap until ready for installation, if the cotton in the protective cap becomes dry, wet it with tap

water. During shipment, air bubbles may have entered the electrode, carefully shake the electrode downward (like a

thermometer) to dispel the air from the sensing elements inside the electrode. Before using the sensor, remove the cap.

!

Figure 6. Smart pH Sensor and Flow Switch Wiring

pH

FLOW

INSIDE

THE

FLOW SENSOR

The flow sensor is used to indicate that there is flow and that it is OK to feed chemicals . The Smart pH will not

allow chemicals to feed if the water flow is not on and detected.

Route the sensor wires through the small strain relief into the Smart pH and to the appropriate connectors

(green terminal bar) in the Smart pH (see Fig. 5).

Do not stuff excess wire inside the controller as this may cause excess strain on sensor and relay connections.

Do not cut the sensor wires.

If the cable is longer than needed, it should be coiled neatly and attached under the controller enclosure.