Electrical Input
Nominal Voltage
120 Vac and 230 Vac; See
Model Selection Guide for
user-selectable voltages
Input Voltage Range
120V: 80 –144 Vac
230V: 120/140/160-276 Vac
Input Power Factor
>.95%
Operating Frequency
50/60Hz, Auto-sensing
Frequency Range
45-65Hz
Input Protection
Fuse or circuit breaker
Electrical Output
On Utility Voltage Regulation
±2% of nominal
On Battery Voltage Regulation
±3% of nominal
Nominal Output Voltage
Same as selected input voltage
Output Voltage Waveform
Sine Wave
Output Voltage Distortion
<3% THD
Output Protection
Electronic overload sensing, and
circuit breaker protection
Efficiency
Online Mode: >86%;
Hi-Efficiency Mode: >90%
Communications
User Interface
LCD status screen
Audible Alarms
UPS alarm conditions, including:
On-Battery, Low Battery, Overload,
UPS Fault
Network Transient Protector
In and out jack for all models.
UL497A tested
REPO Port
Meets NEC code 645-11 intent and
UL requirements
Communications
One RS232 Serial Port; One
Communications Slot;
One USB Port
Communications Cable
6-foot communications cable
included
Power Management Software
Powerware Software Suite CD,
free updates on
www.powerware.com
Technical Specifications
1
General
Topology
True Online, double-conversion
Diagnostics
Full System self-test on power up
UPS Bypass
Automatic on Overload or
UPS failure < 4ms
Transfer Time to Battery
0 ms
Dimensions and Weights
See Model Selection Guide
Overload Capacity
125% for 10 minutes before
transfer to bypass; 150% for 10
seconds before transfer to bypass
Battery
Internal/EBM Battery Type
Sealed, lead-acid; maintenance free
Battery Runtime
See Battery Runtime table
Battery Replacement
Hot-swappable internal and
external batteries
Recharge Time
<4 hours to 90% capacity
Start-On-Battery
Allows start of UPS without
utility input
Environmental
Safety Certifications
120V: UL1778; cUL22.2 NO. 107.1;
230V: CE marked, EN 50091-1-1
and IEC 60950
EMI Compliance
FCC Part 15, Class B (700-1500),
Class A (2000-3000) 230V, EN
50091-2 Class B (700-1500),
Class A (2000-3000)
Operating Temperature
0 to 40
0
C (32 to 104
0
F)
Storage Temperature
-15 to 50
0
C (5 to 122
0
F)
Relative Humidity
0% to 95% non-condensing
Immunity
IEEE C62.41,
IEC 61000-4 -2, -3, -4, -5
Network Transient Protector
UL497A
Audible Noise at 1 meter
700-1000VA: <45dB; 1500VA
<50dB; 2000-3000 <52dB
Altitude
3000m (10,000 ft) without
deteriorating
1. Due to continuing product improvement programs, specifications are subject to change
without notice.
Model Selection Guide
Available Options
Order Number
Description
IPK-0329
ConnectUPS-BD SNMP/WEB Card
1014018
AS/400 Relay Card
Powerware 9120 Family
1. Also user-selectable for 100, 110 and 127 Vac. 2. Automatic frequency selection. 3. 120V models have 6-ft attached line cord. 230V models have 6-ft detachable line cord.
4. Divided into 2 load segments (receptacle groups). 5. Also user-selectable for 220 and 240 Vac.
Model
Power Out
Input/OutPut
Frequency
Input
Output
Dimensions
Weight
(VA/Watt)
Voltage (Vac)
(Hz)
2
Connection
3
Receptacles
4
(H x W x D) in/mm
(LB/KG)
120 Vac Models
1
PW9120 700
700/490
120
50/60
5-15P
(4) 5-15R
9.6 x6.2 x16.2/
243 x 158 x 412
29/13.2
PW9120 1000
1000/700
120
50/60
5-15P
(4) 5-15R,
9.6 x 6.2 x 16.2/
(2) 5-20R
243 x 158 x 412
35.5/16.1
PW9120 1500
1500/1050
120
50/60
5-15P
(4) 5-15R,
10.8 x 6.7 x 17.5/
(2) 5-20R
275 x 170 x 444
46.5/21.1
PW9120 2000
2000/1400
120
50/60
5-20P
(6) 5-20R
14.2 x 8.6 x 18.6/
361 x 217 x 472
82/37.2
PW9120 3000
3000/2100
120
50/60
L5-30P
(4) 5-15R,
14.2 x 8.6 x 18.6/
(2) 5-20R,
361 x 271 x x 472
89/40.5
(1) L5-30R
PW9120 3000h
3000/2100
120
50/60
Hardwired
Hardwired
361 x 271 x x 472
89/40.5
208 Vac Models
PW9120 3000
3000/2100
208
50/60
L6-20P
(2) L6-15R,
14.2 x 8.6 x 18.6/
(1) L6-20R, (1) L6-30R 361 x 217 x 472
89/40.5
230 Vac Models
5
PW9120 700i
700/490
230
50/60
IEC-C14
(4) IEC-C13
9.6 x 6.2 x 16.2/
243 x 158 x 412
28/12.6
PW9120 1000i
1000/700
230
50/60
IEC-C14
(4) IEC-C13
9.6 x 6.2 x 16.2/
243 x 158 x 412
34/15.3
PW9120 1500i
1500/1050
230
50/60
IEC-C14
(4) IEC-C13
10.8 x 6.7 x 17.5/
275 x 170 x 444
44/19.8
PW9120 2000i
2000/1400
230
50/60
IEC-C14
(4) IEC-C13,
14.2 x 8.6 x 18.6/
(1) IEC-C19
361 x 217 x 472
81.6/37
PW9120 3000i
3000/2100
230
50/60
IEC-C20
(4) IEC-C13,
14.2 x 8.6 x 18.6/
(1) IEC-C19
361 x 217 x 472
85/38.5
Optional Extended Battery Modules (EBMs)
PW9120 BATT 700
–
–
–
Standard
–
9.6 x 6.2 x 16.2/
Connector
243 x 158 x 412
31/14
PW9120 BATT 1000
–
–
–
Standard
–
9.6 x 6.2 x 16.2/
Connector
243 x 158 x 412
44/20
PW9120 BATT 1500
–
–
–
Standard
–
10.8 x 6.7 x 17.5/
Connector
275 x 170 x 444
57/26
PW9120 BATT 2000
–
–
–
Standard
–
14.2 x 8.6 x 18.6/
Connector
361 x 217 x 472
110/50
PW9120 BATT 3000
–
–
–
Standard
–
14.2 x 8.6 x 18.6/
Connector
361 x 217 x 472
110/50
9120FXA
Revision 6/02
Reprint 6/02
Product Snapshot
As businesses become increasingly dependent
on technology for their fundamental
operation, the need for system availability is
of paramount importance. The Powerware
9120 UPS is designed for those applications
that need maximum protection in the 700 VA
– 3kVA range. With its high-frequency,
double-conversion online topology, providing
nonstop clean sine wave power, advanced
communications and space-saving tower
design, the Powerware 9120 is the ideal
solution for networks, web servers, telecom-
munications applications and other critical
electronic equipment.
In addition to its proven design, the
Powerware 9120 offers Advanced Battery
Management (ABM
®
) and sophisticated
communications to provide maximum system
availability. ABM uses a three-stage charging
technique that not only doubles battery
service life, but optimizes battery charge time
and provides 60-day notification of the end of
useful life for the batteries.
The Powerware 9120’s communications are
flexible, allowing for local, network or remote
monitoring and management. The Powerware
9120 includes the latest version of Powerware’s
Software Suite, which provides power monitoring
and shutdown software.
Simple plug-and-play operation makes
installing the Powerware 9120 fast and easy. A
single button touch provides clean, uninter-
ruptible power to the critical load. An intuitive
LCD screen provides real-time updates of UPS
status, power usage, battery run time remaining,
and other critical UPS parameters.
With the Powerware 9120, Powerware delivers
a best-in-class power solution for maximum
system availability, and peace of mind.
Powerware
®
9
120
UPS
Features
Ī True double conversion online
technology give you protection from
all nine power problems
Ī Simple installation and operation
Ī Intuitive LCD screen provides real-
time updates of UPS status, power
usage, battery run time remaining
and other critical UPS parameters
Ī Hot-swappable batteries
Ī Extended run time capability with
external battery modules
Ī Complete offering of power
management software included to
ensure data integrity
Ī User-selectable High
Efficiency Mode
Ī Warranty (US and Canada)
- 2-year limited warranty
- 10-year pro-rated warranty
- $25,000 load protection guarantee
Power Rating: 700-3000VA
Voltage: 120 and 230 Vac
Frequency: 50/60 Hz
(auto-sensing)
Configuration: Tower
Invensys Powerware Division
8609 Six Forks Road
Raleigh, NC 27615 U.S.A.
Toll Free: 1.800.356.5794
or 919.872.3020
Fax: 1.800.753.9433
www.powerware.com
Europe
Finland: 358 94 52 661
France: 33 1 6012 7400
Germany: 49 7841 666 0
Italy: 39 02 6600661 2
UK: 44 (0) 1753 608700
Southeast Asia
Singapore: 65 6861 0377
China and North Asia
Hong Kong: 852 2745 6682
Japan
Shinagawa, Tokyo: 81 3 3447 4441
Australia and South Pacific
Sydney, Australia: 61 29878 5000
Canada
Toronto, Ontario: 416.798.0112
Brazil
Sao Paulo, Brazil: 55 11 3845
4369/ 55 11 3704 3632
Mexico
Col. Napoles, Mexico:
525.488.3333