4300 analog multi detector – Panasonic 4300 User Manual
Page 2

All technical features and data are subject to changes without notice, resulting from continuous development and improvement.
Product Leaflet
Date of issue
Revision / Date of revision
MEW00307 2003-04-24
6
/
2008-09-15
Type number
4300
Analog multi detector
+
COM loop
Ext. LED
SA (L)
SA (L)
C.i
.e
. EBL5
12
/ EBL
128
C
O
M
lo
op
in
p
u
t
SB (C)
SB (C)
SB
SB
E-
E-
SA
SA
E+
E+
Mark
Mark
SB
E-
SAo
E+
Mark
SAi
3312
4313
3312FL/F
In the detector:
See also "Engineering Instructions for detectors Type 430x".
SA/SB Contact pins for COM loop / address setting tool 3314
E+/E- Contact pins for External LED
Tl
Type number label; Detector type
Al
Address label; For the programmed COM loop address to be written.
Lsh
Locking screw hole (prepared for drilling through detector body)
Ls Locking
screw
Prepared for mechanical locking with analog base 3312x / 4313. One hexagon socket screw
(Ls) is attached (1.5 mm Hex key to be used). The 2.5-2.7 mm hole (Lsh) has to be drilled.
Technical data
Voltage (V DC)
rated
allowed
normal (on COM loop)
28
12-30
24
Current consumption at nom. volt.
from COM loop (mA)
quiescent
active (incl. internal LED)
ext. LED (connected via base 3312)
0.3
2.3
max. 2
Ambient temperature (
°C)
operating
storage
-10 to +50
-25 to +75
Ambient humidity (% RH)
max. 95, non condensing
Ingress Protection rating (estimated)
IP 51
Sensitivity (obscuration; %/m)
NORMAL mode
2330 mode
Depending on mode.
3.6 / 3.0 / 2.4 (Low / Normal / High)
5
>2.5 in combination with temp. rate-of-rise (depending on algorithm)
Sensitivity (T=
°C; deltaT=
°
C/min.)
NORMAL mode
2330 mode
Depending on mode.
56 / 46 / 60 / 74 (A1; < 4 / A1; > 4 / A2 (S) / B (S))
57; 6.43
57; >1.07 in combination with smoke obscur. (depending on algorithm)
Size
∅ x h (mm)
102 x 44
Weight (g)
70
Construction / Colour
Modified polycarbonate / Grey (N8, Munsell colour code)
Approvals
05 EC Certificate no. 0786-CPD-20145; EN54-7 (smoke)
05 EC Certificate no. 0786-CPD-20146; EN54-5 Class P (heat)
SB
SA
E-
E+
Tl
Ls
Lsh
Al
The detector is plugged in the analog base 3312x / 4313.
The COM loop / Ext. LED are connected to the analog base.