Revision / Date of revision
MEW00012 2000-05-15
5
/
2006-08-31
Type numbers
6275
Heat detector, fixed temperature 60
°C, latching
6276
Heat detector, fixed temperature 80
°C, latching
Technical data
Voltage (V DC)
rated
allowed
normal
24
12-30
24
Current consumption at nom. volt.
(mA)
quiescent (detector only)
active (detector only)
Depending on the type of base it is plugged into. For more details, see
the base respectively.
0
Max. 70 (Current limitation in all EBL equipment)
Ambient temperature (
°C)
operating
storage
6275 / 6276
-10 to +40 / -10 to +60
-25 to +70 / -25 to +70
Ambient humidity (% RH)
max. 95, non condensing
Ingress Protection rating (estimated)
IP22
Alarm temp. (fixed temp.)
60
°C (6275), 80°C (6276)
Weight, detector only (g)
70
Colour
grey (N8, Munsell colour code)
Approvals
CE, EN54-5, response grade 1 (6275)
CE, EN54-8, temp. range 1 detector (6276)