beautypg.com

Specifications, Troubleshooting, Service and support – Powerware 3105 User Manual

Page 2: Status indicators, Led & alarm status table

background image

1

2

3

4

5

6

7

8

9

7

8

9

SPECIFICATIONS

Model Numbers

350 VA / 210W
500 VA / 300W
700 VA / 420W

Capacity

TROUBLESHOOTING

Symptom

Possible Cause

Action to Take

UPS will not turn on

SERVICE AND SUPPORT

MA6B412005(2005/01/12)

700VA model (12V- 7AH battery)

STATUS INDICATORS:

The UPS provides both visual and audible status indicators. Visual
indicators consist of two LEDs to represent the following conditions:
On utility power operation
On battery power operation
UPS fault/alarm

LED & Alarm Status Table

UPS Status

Green LED Red LED

Buzzer

Self-test

AC
(Utility)
Mode

DC
(Battery)
Mode

Charging

Charge Off

Low Battery (Self-test)

Over Load

Normal

Over Load

Low Battery

Short / Fault

Over-Battery / Battery Fault

Blink 1(by turns)

ON

ON

ON

ON

ON

Blink 2

Blink 2

Blink 2

X

X

X

X

X

X

X

Blink 2

Blink 2

Blink 2

Blink 2

Blink 2

B1

B2

B4

B1

B4

B3

ON

B5

Notes:
Blink 1: ON 0.5 seconds / OFF 0.5 seconds.
Blink 2: ON 0.25 seconds / OFF 0.25 seconds.
B1: 1 beep / 5 seconds, ON 0.25 seconds / OFF 4.75 seconds.
B2: 3 beeps / 30 seconds, ON 0.25 seconds / OFF 0.25 seconds 3 times, 28.5 seconds OFF.
B3: 2 beeps / 5 seconds, ON, 0.25 seconds / OFF 0.25 seconds 2 times, 4 seconds OFF.
B4: ON 0.5 seconds / OFF 0.5 seconds.
B5: 3 beeps / 5 seconds, ON 0.25 seconds / OFF 0.25 seconds 3 times, 3.5 seconds OFF.

PW3105 350A
PW3105 500A
PW3105 700A

Nominal Input Voltage

Nominal Output Voltage

Frequency

Total 6 Outlets

240Vac

240Vac

50 / 60 Hz auto sensing

3 Battery Backup & Surge Protection

3 Surge Protection only

Lighting / Surge Protection

Transfer Time to Battery/AC

Battery Type

476 Joules

6ms Typical

Maintenance free, Sealed and leak proof lead-acid

battery

350 / 500 VA: 12V 5 AH

750 VA: 12V 7 AH

Battery Specification

Typical Backup Time

Internet / Phone / Fax Protection

Short Circuit Protection

Communication Port

Operating Temperature

Operating Relative Humidity

3 minutes minimum at full rated load

RJ11

Circuit Breaker

USB

0 C to 40 C

0 to 95% non-condensing

Storage Temperature

-15 C to 50C

Net Weight

350VA - 4.8 kg

500VA - 5.5 kg

700VA - 7 kg

Dimensions (W x D x H)

280 x180 x115mm

* Due to continuing product improvement programs, specifications subject to change
without notice.

The battery is disconnected
or utility power is not
available at the wall outlet.
Input Circuit Breaker has
tripped.

Connect the battery (see Connect
Battery) and ensure power is
available at the wall outlet.
Reduce the amount of equipment
plugged into the outlets of the UPS.
Next, reset the circuit breaker by
pushing the plunger back in.

UPS is making a
continuous sound and
the “Overload” indicator
is lighted.

Turn off the UPS and reduce the
amount of equipment connected to
these outlets.

The “Battery Backup &
Surge Protection” outlets
are overloaded.

Removed all connected equipments
from the UPS and charge the battery
at least 8 hours. During this charging
period, turn off the UPS to prevent
unnecessary discharging.
Call for service or you can replace
the battery by ordering one from
your dealer.

The battery is not fully
charged.

Battery is getting older.

UPS does not provide
expected runtime.

Reduce the amount of equipment

plugged into the outlets of the UPS.

Try reducing the load by removing

one piece of equipment at a time to

determine if the problem continues.

The UPS will turn off when the
battery has been depleted during
an extended power outage. Allow
the UPS to re-charge the battery,
before continuing on battery opera
tion.

Ensure the equipment that is to be

protected from a power outage is

plugged into the “Battery Backup &

Surge Protection” outlets.

Contact Powerware Technical
Support

The UPS is overloaded.

The UPS has exhausted
its available run time.

Equipment is connected
to the “surge Protection”
outlets.

The UPS may require
service.

When utility power fails,
connected equipment
loses power

Please have the following information ready:

Model number and serial number
Symptoms of failure or problem
Customer contact information

For additional information and to register your warranty, please visit
www.powerware.com.au

Register your warranty within 30 days and receive an extended pro-rated
warranty and load protection guarantee.

Eaton Power Quality Pty Ltd
119-127 Wicks Road,
North Ryde NSW 2113

For service and support please call your local distributor or the Powerware
Australia National Service and Repair Centre.

Australia freecall 1300 303 059.