beautypg.com

Powerware 9395 User Manual

Page 3

background image

POWERWARE 9395 UPS (650–825 KVA) SINGLE−FEED KIT INSTALLATION

EATON Powerware

®

9395 UPS (650–825 kVA) Single Feed Kit

S 164201773 Rev 1 www.powerware.com

2

5.

Using tie wraps from the single−feed kit (see Table 1), secure cables to the
internal cabinet divider (see Figure 1).

6.

Return to the applicable Powerware 9395 UPS manual to complete the wiring.
Use M12

50mm bolts from the single−feed kit (see Table 1) to install rectifier

input lugs.

Single Feed Jumpers
from Kit (4 per phase)

Rectifier Input
Terminals

Bypass Input
Terminals

Bus Bar
Extensions

1 M12

45mm Bolt, 2 Flat

Washers, 1 Conical Washer,
and 1 Nut from UPS
Hardware Kit (6 places)

1 M12

50mm Bolt from

Single−Feed Hardware Kit
(18 places)
2 Flat Washers, 1 Conical
Washer, and 1 Nut from
UPS Hardware Kit (18 places

1 M12

45mm Bolt, 2 Flat

Washers, 1 Conical Washer,
and 1 Nut from UPS
Hardware Kit (6 places)

1 M12

45mm Bolt, 2 Flat

Washers, 1 Conical Washer,
and 1 Nut from UPS
Hardware Kit (6 places)

NOTE Install bus bar extensions to back side of rectifier input bus bars to provide clearance for bolts and wires.
NOTE Verify each rectifier phase terminal is jumpered to the same phase on the bypass terminal.
NOTE Install rectifier input lugs using M12

50mm bolts from the single−feed kit.

Tie Wraps (3 places)

Front

Figure 1. 9395 650–825 kVA UPS Single−Feed Kit