Wiring, Feed-through panel: feed and load wiring – Lutron Electronics Switch User Manual
Page 10

R
10
Installation Guide for Switching Panels
• Use a trough when the switching panel is far away from the distribution panel. Splice neutrals in trough.
• Wire the switching panel similar to a lighting distribution panel. Run feed and load wiring.
• Use the switching panel to provide temporary lighting by leaving the bypass jumpers in place. (See page 16 for
more details.)
N
N
H
H
H
SH
H
SH
H
SH
H
SH
Control Circuit Power:
• Supplies power for internal operation.
• Requires dedicated feed with same
voltage and phase as panel.
• Must be 1/4" (6 mm) away from
PELV (Class 2: USA) control wiring
harness.
• Panel voltage (see pages 2-3)
indicates feed voltage.
• For 230 V
and 240 V
panels,
“Hot” is referred to as “Live”.
Therefore, terminals will be labeled L
and SL.
PELV
(Class 2:
USA)
wiring
entrance
Bypass jumpers:
do not remove
Load
Distribution
panel
Terminal block
Neutral
Ground
Dedicated
hot/live
Feed-Through Panel: Feed and Load Wiring
Power feed
(hot/live)
Switched
hot/live
Load
neutral
Typical load circuit
Control
circuit
power
Wiring
{
277 V
277 V
N
N
N
120 V
277 V
control
feed
120 V
control
feed
OR
120 V
*
277 V
Ground
Ground
Neutral
Neutral
Do not wire to
these terminals
Dual-Voltage Panel: Feed and Load Wiring (120/277 V
only)
XINT8-120FT shown
Wire to either the
120 V
or the 277
V
control feed
terminals, not both.
The terminals for the
unused voltage will
remain empty.
Wire Sizes
• Power Feed (Hot/Live):
#14-#10 AWG (2.5-4.0 mm
2
)
• Switched Hot/Live:
#14-#10 AWG (2.5-4.0 mm
2
)
Circuit
breaker
*Note:
120 V
Hot/Live
terminal is protected by
an internal fuse in case
277 V
is mistakenly
applied. A spare fuse is
also supplied in the panel
terminal block.