ESAB 453cc User Manual
Page 11

11
Input &
GND
Fuse Size
Conductor*
Am ps
CU/AWG
208
64
No. 6
90
220
61
No. 6
80
230
58
No. 6
80
482cc
400
33
No. 10
40
460
29
No. 10
40
575
23
No. 12
30
208
82
No. 4
120
220
77
No. 4
120
230
74
No. 4
120
582cc
400
43
No. 8
70
460
37
No. 8
60
575
30
No. 10
50
* Sized per National Code for 75
o
C rated copper conductors @ 40
o
C
Not more than three conductors in a raceway or cable. Local codes
should be followed if they specify sizes other than those listed above.
Rated Input
100% Duty Cycle Rating
Volts
Am ps
Figure 2.1 Connecting Primary Power Leads
Table 2.1 Recommended Input Conductor Size and
Line Fuses
Figure 2.2 Input Terminal Board
*
Double Link Provided
( ) Connections for 50 Hz
230/460 (220/400)V illustrated with voltage links in
the factory supplied 460 volt configuration.
SECTION 2
INSTALLATION
453CC
553CC
Strain Relief
Rear Panel (Inside View)
TB3 Located on
Fan Bracket
Recommended Cable Strip Lengths
Ground Fault
Switch*
SWITCH
GROUND LUG
NUT
HORSESHOE
5"
10"