Troubleshooting – Liebert Little Glass House User Manual
Page 23

23
TROUBLESHOOTING
PROBLEM
CAUSE
SOLUTION
No Power
60 HZ: Verify F2 fuse not blown by
checking on/off switch. If not lit, fuse is
blown
50Hz: Verify breaker has not tripped.
Filter Clogged
Clean, or replace filter
Refrigerant loss
Verify leak. If refrigerant system needs
repaired, replace ECM.
Hot Gas Bypass Valve set
incorrectly
Set valve correctly per LGH handbook
Squirrel cage free spinning on
evaporator or condenser blowers
Reattach and tighten squirrel cage to
blower shaft
ECM Not Cooling
Clogged Condenser coil
Clean coil
Compressor trips on thermal
overload.
Open LGH doors and let compressor cool.
Turn ECM on and verify compressor is
energized (humming). Verify cold air is
being discharged from evaporator
discharge (right side of ECM).
Fans blowing warm air
Faulty Compressor
Verify Compressor has failed. Replace
ECM. If electrical component has failed
causing compressor not to run, replace
component.
Excessive opening of doors
Reduce the amount of opening. Suggest
external keyboard tray. Turn ECM off
when opening door.
Enclosure not properly sealed
Verify leak and fix or replace gasket
Condensate draining
continuously
Evaporator drain kinked or
clogged
Remove ECM and verify plastic tubing is
attached to drain and not kinked or
clogged.
Defective motor in blower
Replace motor
Excessive vibration or
noise
Defective squirrel cage in blower
Replace squirrel cage, or reattach and
tighten to blower shaft.
ECM is overloaded
Verify the correct UPS and load on UPS. If
no UPS; verify watt load of equipment
does not exceed ECM rating.
Heat not rejected from room
Verify LGH is located in room with air
circulation and heat rejected from ECM is
sufficiently removed from room.
ECM not cooling
See above
Cabinet is excessively
hot
UAS operation
Verify UAS operation by jumpering
terminals on high temperature stat