58 Room Air Conditioner

Troubleshooting Guide

2) Balance refrigerant of the 3-way valve

(Gas leakage)

• Procedure

(1) Confirm that both the liquid side and gas side

valves are set to the back seat.

(2) Connect the charge set to the 3-way valve’s

port.
– Leave the valve on the charge set closed.
– Connect the charge hose to the service port.

(3) Open the valve (Lo side) on the charge set and

discharge the refrigerant until the gauge indi-
cates 0 kg/cm

2

G.

– If there is no air in the refrigerant cycle (the

pressure when the air conditioner is not running
is higher than 1 kg/cm

2

G), discharge the refrig-

erant until the gauge indicates 0.5 to 1
kg/cm

2

G. if this is the case, it will not be neces-

sary to apply a evacuatin.

– Discharge the refrigerant gradually; if it is dis-

charged too suddenly, the refrigeration oil will
also be discharged.

Lo

Open

Open

3-Way
valve

3-Way
valve

Gas side

CLOSE

OPEN

Outdoor unit

Liquid side

Indoor unit