Lightolier L1PH Series User Manual
L1ph, L1ph series uninterruptible power supplies, Overall characteristics

Unit
12.0 kVA
Total Battery
2,365 lbs.
Cabinets
(1073 kg)
Electronics
465 lbs.
Cabinet
(211 kg)
Total System
2,830 lbs.
(1,284 kg)
L1PH Series Uninterruptible Power Supplies
L1PH
Page 1 of 2
12.0 kVA Single Phase UPS System
Lightolier
a Genlyte Thomas Company
www.lightolier.com
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710
We reserve the right to change details of design, materials and finish.
© 2004 Genlyte Thomas Group LLC (Lightolier Division) • D0504
Overall Characteristics
• 86% throughput efficiency
• Operating temperature range 32°F (0°C) to 104°F (40°C)
• Internal maintenance by-pass is standard
• Main load disconnect switch standard
• Double conversion, no interruption
• Standard backup time of 90 minutes, other run times optional
• Output circuit breakers and normally-off loads optional
Housing
• Free standing, NEMA 1 enclosure
• Acid resistant powder coat finish
• Multiple conduit entries
Metering/Controls
Standard
• Alpha-numeric front panel display with 14 metered measurements
and 53 messages/alarms
• Normal, caution and alarm indicating LEDs
• Audible failure alarms with silence switch
• Dry contact for remote failure alarm
• “D” type 9-pin computer interface connector (see pin config. on back)
• Programmable battery monitor with alarm
Optional
• Diagnostics software for remote computer (PC) monitoring and control
• Stand-alone remote display mimics all measurements, indications
and alarms shown on the front panel display
• Additional RS-232 input/output port for remote monitoring and system
control
Electrical
• Sine Wave Output
• Completely solid-state Pulse Width Modulation (PWM) inverter
• 16-bit microprocessor control
• Input power factor correction maintains power factor at 0.99
• Transient response
≤ 5%; Recovery time, 10 mS (100% load step)
• 3:1 crest factor capability
• Inverter output distortion
≤ 2.5% THD (at unity power factor)
• Output voltage regulation ±6% of nominal at full load
• Frequency within ±0.05% of nominal
• Inverter efficiency
≥ 84%
• Load power factor capability is 0.5 leading to 0.5 lagging
(Continued on page 2)
Operates incandescent, magnetic and electronic ballast fluorescent, high power factor compact fluorescent, and high intensity discharge (HID) lamp types.
How to Specify:
Job Information
Type:
Job Name:
Cat. No.:
Lamp(s):
Notes:
NOTE: Input circuit
breaker not available.
Input switch is
standard.
L1PH
I
12.0
S
SERIES
INPUT
SYSTEM
BASE
BATTERY
OUTPUT
OUTPUT
# ON 2ND
NORMALLY
# OF
NOL
VOLTAGE
TYPE
SIZE
TYPE
VOLTAGE
CKT BRKRS
1
VOLTAGE
OFF LOAD
NOL
VOLTAGE
L1PH = Single
Phase
Uninterruptible
Power
Supplies
12.0 = 12.0 kVa
2 = 208 V
3 = 240 V
4 = 277 V
Z = Special
Voltage
(Consult
Factory)
1 = 120 V
2 = 208 V
3 = 240 V
4 = 277 V
5 = 120/208 V
6 = 120/240 V
7 = 120/277 V
Z = Special
Voltage
(Consult
Factory)
Y = Hardwire
A = 1 0CB
B = 2 0CB
C = 3 0CB
D = 4 0CB
E = 5 0CB
F = 6 0CB
G = 7 0CB
H = 8 0CB
J = 9 0CB
K = 10 0CB
L = 11 0CB
M = 12 0CB
N = OCBA1
P = OCBA2
R = OCBA3
S = OCBA4
T = OCBA5
U = OCBA6
V = OCBA7
W = OCBA8
X = OCBA9
0
1
2
3
4
5
6
7
8
9
10
11
A = No
B = Yes
C = Yes w/ Time
Delay Timer
0 = No NOL
Y = Hardwire
Terminal
1 = 1
2 = 2
3 = 3
4 = 4
5 = 5
6 = 6
7 = 7
8 = 8
9 = 9
10 = 10
11 = 11
12 = 12
X = None
A = 1st
B = 2nd
I = ETL Listed
to UL 924 for
Emergency
Lighting
Applications
S = Sealed
Lead Calcium
33.0”
83.8 cm
29.6”
61.0 cm
43.5”
110.5 cm
34.0”
86.4 cm
33.0”
83.8 cm
70.0”
177.8 cm
Battery
Cabinet
Electronics
Cabinet