Table 5.4 Program Functions
Parameter
Format
Factory Default
Date
MM/DD/YY (Month, Date, Year)
Current Date
Time
HH/MM (Hours, Minutes)
Eastern Stand Time
Monthly Test Date
DD (Date)
15
th
of the Month
Monthly Test Time
HH/MM (Hours, Minutes)
5:00
Yearly Test Date
MM (Month)
01
Yearly Test Time
HH/MM (Hours, Minutes)
8:00
Load Reduction
AAAA(Amps)
0.0A
Low VAC Alarm
VVVV(Volts)
1.0V
High VAC Alarm
VVVV(Volts)
999.9V
Ambient Temp Alarm DDD(Degrees Centigrade)
70°C
Near Low Battery
VVVV(Volts)
See Table 5.5
■
Near Low Battery Voltage is in VVVV (Volts). The last digit entered is after the decimal place.
I.E. (430 + ENTER) will register 43.0VDC. Please refer to table 5.5.
■
Load Reduction Fault is in AAAA (Amps). The last digit entered is after the decimal place.
I.E. (480 + ENTER) will register 48.0 Amps. If the output current under battery power is 10
percent below this number, the alarm will be set.
■
Low AC Voltage Alarm is in VVVV (Volts). The last digit entered is after the decimal place.
I.E. (1200 + ENTER) will register 120.0 Volts. If the Input AC Voltage goes below this number
the alarm will be set.
■
High AC Voltage Alarm is similar to Low AC Voltage Alarm.
■
Ambient Temperature Alarm is in DDD (Degrees Centigrade). I.E. (75 + ENTER) will register
75 deg. C. When the ambient temperature internal to the inverter enclosure goes above the
set point the alarm will be set.
Table 5.5 Near Low Battery Voltages
DC Voltage
Near Low Battery
48VDC 43VDC
72VDC 65VDC
96VDC 86VDC
120VDC 108VDC
144VDC 130VDC
180VDC 162VDC
240VDC 216VDC