Kenmore THE ECONOMIZER 153.33206 User Manual
Page 11
11
and 12” (30.5 cm) from the top. (Standard clearance.) If clearances
stated on the heater differ from standard clearances, install water heater
according to clearances stated on the heater.
Adequate clearance for servicing this appliance should be considered
before installation, such as changing the anodes, etc.
A minimum clearance of 5” (12.7 cm) must be allowed for access
to replaceable parts such as the thermostats, drain valve and relief
valve.
When installing the heater, consideration must be given to proper location.
Location selected should be as close to the wall as practicable and as
centralized with the water piping system as possible.
FIGURE 9.
A gas water heater cannot operate properly without the correct amount
of air for combustion. Do not install in a confi ned area such as a closet,
unless you provide air as shown in the “Facts to Consider About the
Location” section. Never obstruct the fl ow of ventilation air. If you have
any doubts or questions at all, call your gas supplier. Failure to provide
the proper amount of combustion air can result in a fi re or explosion and
cause death, serious bodily injury, or property damage.
FIGURE 10.
If this water heater will be used in beauty shops, barber shops, cleaning
establishments, or self-service laundries with dry cleaning equipment, it
is imperative that the water heater or water heaters be installed so that
combustion and ventilation air be taken from outside these areas.
Propellants of aerosol sprays and volatile compounds, (cleaners, chlorine
based chemicals, refrigerants, etc.) in addition to being highly fl ammable
in many cases, will also react to form corrosive hydrochloric acid when
exposed to the combustion products of the water heater. The results
can be hazardous, and also cause product failure.
INSULATION BLANKETS
Insulation blankets are available to the general public for external use
on gas water heaters but are not necessary with Kenmore products.
The purpose of an insulation blanket is to reduce the standby heat loss
encountered with storage tank heaters. Your Kenmore water heater
meets or exceeds the National Appliance Energy Conservation Act
standards with respect to insulation and standby loss requirements,
making an insulation blanket unnecessary.
Should you choose to apply an insulation blanket to this heater, you
should follow these instructions (For identification of components
mentioned below, see Figure 1). Failure to follow these instructions can
restrict the air fl ow required for proper combustion, potentially resulting
in fi re, asphyxiation, serious personal injury or death.
• Do not apply insulation to the top of the water heater, as this will
interfere with safe operation of the blower assembly.
• Do not cover the outer door, thermostat or temperature & pressure
relief valve.
• Do not allow insulation to come within 2” (5.1 cm) of the fl oor to
prevent blockage of combustion air fl ow to the burner.
• Do not cover the instruction manual. Keep it on the side of the
water heater or nearby for future reference.
• Do obtain new warning and instruction labels from Sears
for placement on the blanket directly over the existing labels.
• Do inspect the insulation blanket frequently to make certain it
does not sag, thereby obstructing combustion air fl ow.
COMBUSTION AIR AND VENTILATION FOR APPLIANCES
LOCATED IN UNCONFINED SPACES
UNCONFINED SPACE is space whose volume is not less than
50 cubic feet per 1,000 Btu per hour (4.8 cubic meters per kW) of the
aggregate input rating of all appliances installed in that space. Rooms
communicating directly with the space in which the appliances are
installed, through openings not furnished with doors, are considered a
part of the unconfi ned space.
In unconfi ned spaces in buildings, infi ltration may be adequate to provide
air for combustion, ventilation and dilution of fl ue gases. However, in
buildings of tight construction (for example, weather stripping, heavily
insulated, caulked, vapor barrier, etc.), additional air may need to be
provided using the methods described in “Combustion Air and Ventilation
for Appliances Located in Confi ned Spaces.”
COMBUSTION AIR AND VENTILATION FOR APPLIANCES
LOCATED IN CONFINED SPACES
CONFINED SPACE is a space whose volume is less than 50 cubic feet
per 1,000 Btu per hour (4.8 cubic meters per kW) of the aggregate input
rating of all appliances installed in that space.