beautypg.com

Troubleshooting guide, Start up conditions – Kenmore POWER MISER 153.33066 User Manual

Page 26

background image

26

TROUBLESHOOTING GUIDE

Start Up Conditions

Thermal Expansion

As water is heated, it expands (thermal expansion). In a closed
system, the volume of water will grow. As the volume of water
grows, there will be a corresponding increase in water pressure
due to thermal expansion. Thermal expansion can cause
premature tank failure (leakage). This type of failure is not
covered under the limited warranty. Thermal expansion can also
cause intermittent temperature-pressure relief valve operation:
water discharged from the valve due to excessive pressure build
up. The temperature-pressure relief valve is not intended for the
constant relief of thermal expansion. This condition is not covered
under the limited warranty.

A properly-sized thermal expansion tank should be installed
on all closed systems to control the harmful effects of thermal
expansion. Contact a plumbing service agency or your retail
supplier regarding the installation of a thermal expansion tank.

Tabel 1: Thermal Expansion Tank Specifi cations

Model

Number

Tank

Capacity

In Gallons

Dimensions

in Inches

Pipe

Fitting

On Tank

Diameter

Length

153.331020

2

8 (203 mm) 12-3/4 (323 mm) 3/4” Male

153.331050

5

11 (279 mm) 14-3/4 (375 mm) 3/4” Male

Table 2: Expansion Tank Sizing Chart

Expansion

Tank

Capacity

Needed

Inlet*

Water

Pressure

Water Heater Capacity (Gallons)

30

40

50

66

82

40 psi

2

2

2

5

5

50 psi

2

2

2

5

5

60 psi

2

2

2

5

5

70 psi

2

2

5

5

5

80 psi

2

5

5

5

5

*Highest recorded inlet water pressure in a 24 hour period or
regulated water pressure.

NOTE: Expansion tanks are pre-charged with a 40 psi air
charge. If the inlet water pressure is higher than 40 psi, the
expansion tank’s air pressure must be adjusted to match
that pressure, but must not be higher than 80 psi.

FIGURE 35.

Strange Sounds

Possible noises due to expansion and contraction of some metal
parts during periods of heat-up and cool-down do not represent
harmful or dangerous conditions.

Condensation causes sizzling and popping within the burner area
during heating and cooling periods and should be considered
normal. See Condensation section.

Draft Hood Operation

Check draft hood operation by performing a worst case
depressurization of the building. With all doors and windows
closed, and with all air handling equipment and exhaust fans
operating such as furnaces, clothes dryers, range hoods and
bathroom fans, a match fl ame should still be drawn into the
draft hood of the water heater with its burner fi ring. If the fl ame
is not drawn toward the draft hood after 15 minutes of burner
operation, shut off water heater and make necessary air supply
changes to correct.