beautypg.com

Studer Innotec RCC-03 User Manual

Page 42

background image

Studer Innotec

42

The auxiliary contact will only be activated after the battery exceeds again a certain voltage value

and also after a duration, both independently of the activation parameters.
This voltage and this duration are programmable too.
• Dynamic compensation of the thresholds {1288} {1354}

• Voltage 1 active {1246} {1355}
• Voltage 1 {1247} {1356}

• Duration 1 {1248} {1357}

• Voltage 2 active {1249} {1358}
• Voltage 2 {1250} {1359}

• Duration 2 {1251} {1360}

• Voltage 3 active {1252} {1361}
• Voltage 3 {1253} {1362}

• Duration 3 {1254} {1363}

• Voltage for deactivation of the auxiliary contact {1255} {1364}
• Duration over battery voltage for deactivation {1256} {1365}

• Deactivate if the battery is in floating mode {1516} {1517}

Dynamic compensation of the thresholds {1288} {1354}
If the contacts are activated according to the battery voltage, you can use the voltage

compensated dynamically for each threshold.
If this function is not activated, then the average battery voltage will be used.

If this function is activated, the real battery voltage is compensated according to power used.

Deactivate if the battery is in floating mode {1516} {1517}
If you activate one of the auxiliary contacts according to the battery voltage, you can force the

deactivation if the battery is in floating mode. In this way, even if the deactivation voltage is not

reached or if the duration of the voltage deactivation is not completed, the auxiliary contact will
be released.

Contacts activated by inverter power or smart boost {1257} {1366}

If the power output of the inverter exceeds a certain level, the contact may be activated. The

exceedance is linked to a duration. Three power levels linked to three durations are configurable to
activate the auxiliary contact.

The auxiliary contact will only be activated after the output power passes below a value and

during a duration, both independently of the activation configurations.
If the smart boost function is active, these configurations are also taken into account with the

power of the boost.
• Power 1 active {1258} {1367}

• Power 1 {1259} {1368}

• Duration 1 {1260} {1369}
• Power 2 active {1261} {1370}

• Power 2 {1262} {1371}

• Duration 2 {1263} {1372}
• Power 3 active {1264} {1373}

• Power 3 {1265} {1374}

• Duration 3 {1266} {1375}
• Power for deactivation of the auxiliary contact {1267} {1376}

• Duration below power for deactivation {1268} {1377}

Contacts activated with set schedules {1269} {1378}

The auxiliary contact can also be activated like a programmable clock. Three different weekly
programs are available.

For each program, the time frame may be applied to one or several days of the week.

If the finishing time is programmed before the starting time, the time frame is not taken into
account.
• Program 1 {1270} {1379}

o

Days of the week {1271} {1380}

o

Time of start of activation {1272} {1381}

This manual is related to the following products: