5 programming – Studer Innotec C 1600-12 User Manual
Page 19

STUDER INNOTEC
COMPACT
User manual
COMPACT V4.0 E
19
Caution: No external voltage should be connected to this Input Control.
4.11 The Temperature sensor
Operating voltage of lead-acid batteries change depends on the 
temperature. To correct the operating voltages according to the actual 
temperatures, a temperature sensor can be connected to the COMPACT. 
The compensation through the sensor is –3mV/°C/Cell. 
 
Order Number: CT-35 
Dimensions: H x B x T / 58 x 51.5 x 22mm 
5 Programming
5.1 Standard
setting
The COMPACT is delivered with the default setting following:
5.1.1 Working
mode
The working of the charger, the inverter and the transfer are described in chapter 5.3/5.4/5.5.
5.1.2 Battery
voltage
Low voltage
11.6V / 23.2V / 46.4V
Float Charge
13.5V / 27.0V / 54.0V
End of Charge Voltage
14.4V / 28.8V / 57.6V
Equalization
15.3V / 30.6V / 61.2V
Absorption Time:
2 Hours
5.1.3 Auxiliary
contact
Active in case of defect or manual turn off with the LED 10/11/12/13
5.2 Reset
value
When the COMPACT is to be connected to a battery or after an interruption (RESET), it is always 
programmed with these standard settings. 
In order to get to these settings during operation you must press the three Push Buttons 19/20/21 
simultaneously for a minimum of 2 seconds. 
5.3 Battery voltages and absorption time
The voltage levels (low voltage, float charge, end of charge and equalization) and the duration of 
the absorption charge can be changed. 
The display of these voltages and the times in the program mode are in accordance with the 
diagram shown below: 
 
5.3.1 Table of voltage and timing threshold 
 
 Low 
voltage
LED 13
Float Charge 
LED 12 
Absorption 
LED 11 
Equalization 
LED 10 
Absorpt. 
Time 
LED 10->13 
LED 12V 24V 48V 12V 24V 48V 12V 24V 48V 12V 24V 48V 12/24/48V 
14 12.0 24.0 48.0 13.7 27.4 54.8 16.2 32.4 64.8 16.2 32.4 64.8 4 
h
15 11.8 23.6 47.2 13.6 27.2 54.4 15.6 31.2 62.4 15.9 31.8 63.6 3
h
16 11.6 23.2 46.4 13.5 27.0 54.0 15 30 60 15.6 31.2 62.4 2
h
17 11.4 22.8 45.6 13.4 26.8 53.6 14.4 28.8 57.6 15.3 30.6 61.2 1
h
18 11.2 22.4 44.8 13.3 26.6 53.2 14.2 28.4 56.8 15 30 60 0
–
1Min.
The heavy printed values show the standard settings.