FILL: Heat transfer fill media shall be crosscorrugated

20 mil PVC sheets supported by stainless steel tubes

which, in turn, are suspended by stainless steel tension

hangers from concrete support beam members.

DRIFT ELIMINATORS: Drift eliminators shall be

supplied in a 3 pass cellular arrangement of bonded

17 mil PVC sheets. Drift loss shall not exceed ______%

of circulating water.

HOT WATER DISTRIBUTION SYSTEM: Hot water

distribution system in each cell shall be supplied with

a single interior inlet terminating 1'-0 below bottom of

the tower filling. Materials will be of inert PVC and RTR

and polypropylene piping supported by the support

beams utilized to carry heat transfer fill media.

FAN CYLINDERS: Fan cylinders shall have eased inlet

design and be of molded fiber reinforced polyester

with a minimum height of 6' 0.

OPTlONS: Factory Mutual Approval. The tower

shall include all design and material modifications

necessary to meet the fire rating requirements of

Factory Mutual. The product proposed shall be listed

in the FM Approval Guide, latest edition.
Masonry structure options at owner’s election:
1-Shell structure design shall be by cooling tower

manufacturer.
2-Shell structure and cold water basin design shall be

by cooling tower manufacturer.
3-Shell structure and cold water basin design shall

be by cooling tower manufacturer. Shell structure

construction including materials and labor shall be

by cooling tower manufacturer.
4-Shell structure and cold water basin design shall be

by cooling tower manufacturer. Shell structure and

cold water basin construction including materials and

labor shall be by cooling tower manufacturer.

WARRANTY: Warranty on all components against

defective materials and workmanship will be

extended for a period of one (1) year following initial

operation but not exceeding eighteen (18) months

from date of shipment. Components that may fail

within warranty period shall be repaired and/or

replaced including freight and installation labor.
Thermal testing of cooling tower will be done

within one (1) year following structural completion

in accordance with Cooling Technology Institute

Acceptance Test Code CTI ATC 105. In the event test

results indicate deficiency, manufacturer shall make

alterations to overcome indicated deficiency and if

such alterations are inadequate manufacturer shall

refund a percentage of contract price proportional to

tower deficiency.

SPECIFICATIONS

COOLING TOWER: Furnish and install (1) Induced

Draft Counterflow Cooling Tower. Cooling tower

shall be______ft. long x ______ft. wide x ______ ft.

overall height with a maximum operating weight

of______lbs. Cooling tower shall consist of_____fan

cells with a maximum of_____total fan horsepower

and a maximum pump head of______ft.
Other contractor(s) will furnish all external piping,

valves, pumps, electrical equipment other than

cooling tower fan motors, wiring, controls, etc. all in

accordance with general overall dimensions to be

supplied by cooling tower manufacturer. All internal

components of cooling tower as described following

will be furnished and installed by the cooling tower

manufacturer.

CAPACITY: Cooling tower shall be selected and

guaranteed to cool______GPM of water from

______°F to ______°F at ______°F entering wet bulb

temperature.

MECHANICAL EQUIPMENT: Mechanical equipment

shall be designed specifically for cooling tower usage

and shall be mounted on a rigid unitized HDG steel

support to assure permanent drivetrain alignment.

Cooling tower manufacturer shall be responsible for

equipment warranty.

FANS: Fans shall be of a multi-blade propeller

type and blades shall be constructed of solid glass

reinforced polyester, cast aluminum alloy or hollow

glass reinforced epoxy. Hubs shall be HDG steel cast

iron or aluminum plate. Blades shall be individually

adjustable for required pitch angles.

DRIVESHAFTS: Driveshaft tubes and flanges shall be

manufactured of type 304 stainless steel. Couplings

shall be hot dip galvanized cast iron, joined to

the driveshaft by flexible neoprene bushings and

cadmium plated steel inserts. Connecting hardware

shall be 300 stainless steel. Driveshaft assemblies shall

be dynamically balanced at the factory at full motor

speed.

SPEED REDUCERS: Speed reducers shall be provided

for right angle fan drive and shall be designed to

AGMA standards for continuous duty operation,

capable of reverse operation. Oil fill and drain lines

are to be extended outside the fan cylinder to an oil

level sight glass.

ELECTRIC MOTORS: Electric motors shall be_______

speed, single winding, variable torque, _____ hp

maximum, TEFC, and specially insulated for cooling

tower duty. Speed and electrical characteristics shall

be _____ RPM, _____ phase, _____ hertz, _____ volts.

If the load applied to the motor exceeds 90% of the

nameplate rating, then the motor shall have a 1.15

service factor and the service factor beyond 1.0 shall

not be considered available for load.