SUGGESTED SPECIFICATION

(Natural or Propane) gas water heater(s) shall be State Force™ 90+ model SHE50 100NE, with 96% thermal efficiency, a storage capacity of 50 gallons, an input rating of 100,000 BTU per hour, a recovery
rating of 116 gallons per hour at 100ºF rise and a maximum hydrostatic working pressure of 150 psi. Water heater(s) shall be of power direct vent design, using 2 or 3˝ PVC, CPVC or ABS pipe for horizontal and/or
vertical vent runs. Water heater(s) shall have: 1: Glasslined steel tank construction and a spiral-shaped heat exchanger placed entirely inside the tank, which shall be glasslined on the flue gas side to
protect against acidic condensate. 2: Advanced electronic control with large LCD display and advanced diagnostics. Water heaters shall incorporae the iCOMM

system for remote monitoring, leak detection and

fault alert. 3: A 3-year limited warranty against tank leaks. Water heater(s) shall meet the thermal efficiency and standby loss requirements of the U.S. Department of Energy and current edition of
ASHRAE/IESNA 90.1.

F

ORCE

90+

96% Efficient
Power Direct Vent Commercial Gas Water Heaters

All models–Maximum Supply Pressure: 14 inches w.c. (3.48 kPa) Minimum Supply Pressure Natural Gas: 3.5 inches w.c.
(.87 kPa). Minimum Pressure Propane: 8.0 inches w.c. (1.99 kPa). Minimum Pressure must be maintained under both load and no-load (static and dynamic)
conditions.

SPECIFICATIONS

DIMENSIONS

SHE50 100NE

A

B

C

D

E

F

INCHES

66-3/4

49-1/4

22

15-3/4

3

8

MODEL

NUMBER

BTU

INPUT

PER

HOUR

TANK

SIZE

GALLONS

RECOVERY–GALLONS

PER HOUR

AT DEGREE RISE

SHIPPING

WEIGHT

LBS.

40ºF

100ºF

140ºF

SHE50 100NE

100,000

50

291

116

83

255

Top inlet and outlet: 3/4˝ male NPT

Side inlet and outlet: 3/4˝ female NPT

Gas inlet: 1/2˝ NPT

Optional Concentric Vent Kit

Part # 9003910105

Revised June 2013

*INSTALL IN ACCORDANCE WITH LOCAL CODES.