Installation – Siemens Type Vector E50001-F710-A420-X-4A00 User Manual

Page 12

background image

Installation

8. Remove single-point lift bracket.

9. Ground the air switch unit (and surge

arresters if required) using #2 or larger
copper wire. A grounding point (1/2-13
tapped hole) is provided in the side of
the mounting bracket (refer to
assembly drawing provided).

10. Mount pipe guides and lock segment

assemblies in position per user's
construction standard or assembly
drawing using one through bolt and
one lag bolt each. Tighten the through
and lag bolt.

Note: The pipe guides and lock segment
are adjustable. Loosen the bolts such that
the pipe guides and lock segment can slide
in the slots (refer to Figure 5: Loosen
bolts).

11. Install vertical operating shaft sections

and universal joint as shown on the
assembly drawing using pins, cotter
keys, coupling assemblies (if required)
and insulator assembly (if required).
Before placing bottom shaft section in
the lock segment, place the operating
handle assembly loosely in position.

Figure 5: Loosen bolts

Item

Description

A

Loosen bolt

A

Note: Verify the piercing set screws are
backed out all the way before sliding the
handle assembly on the bottom shaft
section (refer to Figure 6: Before piercing).

A

A

A

Figure 6: Before piercing

Item

Description

A

End of piercing set screws must
not extend beyond this surface.

A

Before piercing

12. Excess pipe should be removed if

required. Leave at lease 1' (.3 m) of
pipe extending below the lock
segment assembly.

OPEN

CL

OSED

12