Calibrator connected to display pcb – Siemens Remote Displays SITRANS RD100 User Manual
Page 9
7ML19985JU01
SITRANS RD100 – INSTRUCTION MANUAL
Page 7
Calibrator connected to display PCB
WARNINGS:
• To maintain hazardous area protection, the input signal must
always be connected to the input signal PCB, and not directly to
the display PCB.
• Electrostatic hazard. Clean only with a moist cloth. Protect
enclosure from exposure to chemical solvents and excessive
ultraviolet (UV) light (such as sunlight).
display PCB
component side
calibrated
current source
S-
S+
DP2
DP3
DP1
The display PCB may be removed from the enclosure for bench calibration.
Loop jumper must be installed on input signal PCB to maintain loop. Refer to