Wiring the 480V Power Supply

9200 Power Supply Retrofit Instructions

Page 4

Wiring the 480V Power Supply

480V Power Supply

Connect one phase to the L1 terminal and the other phase to the L2 terminal. You
can use the same wires from the grid that the voltage inputs use (see diagram
above).

The power supply G (ground) terminal must be connected to the same point as the
meter

terminal.

Protective Fuses

The 480V power supply requires 100 mA fuses on the L1 and L2 terminals. These
should be IEC type T slow blow fuses.

N

OTE

100 mA fuses can be shared with the voltage inputs.

Powering Up the Meter

After the power supply is attached to the meter, and its wiring is connected:

1.

Reconnect and energize all wiring that was disconnected when the meter was
prepared for power supply installation.

2.

Power up the meter and verify correct operation.

100 mA fuses

on L1 and L2

Use18 to 14 AWG
(0.8mm

2

to 2.1mm

2

) wires

Connections to the

L1 and L2 terminals

can come from V1

and V2

Use18 to 14 AWG
(0.8mm

2

to 2.1mm

2

) wire