Sunlife Enterprises SUNLINE DM180 User Manual
Page 28

356214-XIM-A-0108
28
Johnson Controls Unitary Products
NOTES: 1.Blower performance includes fixed outdoor air, 2” T/A filters, a dry evaporator coil and no electric heat.
2.Refer to Table 16 for additional static resistances.
ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total
static pressure of the blower.
* Do NOT close the pulley below 1 turn open.
** Factory setting.
TABLE 11: SUPPLY AIR BLOWER PERFORMANCE (15 TON) - COOLING ONLY
180 MBH - BOTTOM DUCT CONNECTIONS
BLOWER
SPEED,
(RPM)
MOTOR
PULLEY
(TURNS
OPEN)*
AIRFLOW
2.10 m
3
/s
2.45 m
3
/s
2.80 m
3
/s
3.10 m
3
/s
3.40 m
3
/s
ESP
(Pa)
Output
(kW)
Input
(kW)
ESP
(Pa)
Output
(kW)
Input
(kW)
ESP
(Pa)
Output
(kW)
Input
(kW)
ESP
(Pa)
Output
(kW)
Input
(kW)
ESP
(Pa)
Output
(kW)
Input
(kW)
HIGH STATIC DRIVE (m
3
/s)
1030
6.0
357
2.4
2.8
316
2.8
3.4
253
3.3
3.9
183
3.7
4.5
97
4.2
5.0
1070
5.0
405
2.5
3.0
362
3.0
3.6
298
3.5
4.2
226
3.9
4.7
-
-
-
1115
4.0
461
2.7
3.2
416
3.2
3.8
351
3.7
4.4
278
4.2
5.0
-
-
-
1155
3.0
514
2.9
3.4
468
3.4
4.0
401
3.9
4.7
-
-
-
-
-
-
1200
2.0
577
3.1
3.7
529
3.6
4.3
461
4.1
5.0
-
-
-
-
-
-
1240
1.0
636
3.3
3.9
587
3.8
4.5
-
-
-
-
-
-
-
-
-
BLOWER
SPEED,
(RPM)
MOTOR
PULLEY
(TURNS
OPEN)*
AIRFLOW
4450 CFM
5190 CFM
5930 CFM
6565 CFM
7200 CFM
ESP
(iwg)
Output
(bhp)
Input
(kW)
ESP
(iwg)
Output
(bhp)
Input
(kW)
ESP
(iwg)
Output
(bhp)
Input
(kW)
ESP
(iwg)
Output
(bhp)
Input
(kW)
ESP
(iwg)
Output
(bhp)
Input
(kW)
HIGH STATIC DRIVE (CFM)
1030
6.0
1.4
3.2
2.8
1.3
3.8
3.4
1.0
4.4
3.9
0.7
5.0
4.5
0.4
5.6
5.0
1070
5.0
1.6
3.4
3.0
1.5
4.0
3.6
1.2
4.7
4.2
0.9
5.3
4.7
-
-
-
1115
4.0
1.9
3.6
3.2
1.7
4.3
3.8
1.4
5.0
4.4
1.1
5.6
5.0
-
-
-
1155
3.0
2.1
3.9
3.4
1.9
4.5
4.0
1.6
5.2
4.7
-
-
-
-
-
-
1200
2.0
2.3
4.1
3.7
2.1
4.8
4.3
1.8
5.5
5.0
-
-
-
-
-
-
1240
1.0
2.6
4.4
3.9
2.4
5.1
4.5
-
-
-
-
-
-
-
-
-