Marley, Sigma 1000, Cooling tower – SPX Cooling Technologies 1000 User Manual
Page 7: Engineering data : concrete basin
Marley
/
Sigma 1000
Cooling Tower
/
Engineering Data : Concrete Basin
7
NotE
1 Use this bulletin for preliminary layouts only. Do not use for
construction. Obtain current drawings from your Marley sales
representative. Concrete basin design and construction are by
other contractors or purchaser.
2 Operating weight is total wet operating weight of tower only,
excluding water in concrete basin.
3 Maintain at least 2'-0" of clear space at endwall faces for
construction purposes. Air inlet faces must have unobstructed
air supply. Consult your Marley sales representative for
recommendations if nearby obstructions may interfere.
4 Minimum basin depth is 1'-6". Maximum basin depth is 5'-6".
Extended interior columns for deep basins are available as an
option. Perimeter columns remain at 1'-6" below top of basin
curb.
5 All anchor bolts complete with nut and washer must be
furnished by others. Bolts must be
3
⁄
4
"diameter with 2" all-thread
projection.
6 Other contractors or purchaser must design, construct, and
furnish sump and overflow to suit requirements.
Tower
Model
Dimensions
Operating Weigt lb
W
A
B
Single Cell
Each Cell Add
1011
21'-10"
2
8'-0"
15120
13500
1021
21'-10"
3
12'-0"
20160
18400
1031
24'-2"
3
12'-0"
21240
19500
1041
26'-5"
4
16'-0"
29020
27200
1’-6
1'-0 RECOMMENDED
OPERATING WATER LEVEL
1’-6
1'-0 RECOMMENDED
OPERATING WATER LEVEL
A
BAYS @ 4'-0" =
B
PER CELL
6"
AIR INLET FACE
CL
COL.
CL COL.
6" MIN.
6" MIN.
6"
W
IN
TO IN OF BASIN W
ALLS
AIR INLET FACE
ENDW
ALL
F
ACE
ENDW
ALL
F
ACE
6" MIN.
6" MIN.
FLAt BAsiN sEctioN
dEEP BAsiN sEctioN
PLAN