5 microprocessor control, 1 introduction, 2 setting the process water temperature – Sterling Power Products SMC 1/2 - 1 1/2 Portable Chiller User Manual
Page 26: 3 led indicators
Page 26
SMC Series Chillers
5 Microprocessor
Control
5-1 Introduction
Standard SMC Series chillers use a microprocessor-based PID controller. The
controller is a modular, self-contained unit that can slide from its mounting housing. It
is factory set and adjusted; no field adjustment to the internal controls is necessary.
SMC Control Operation Range
Standard models
30°F to 65°F (-1ºC to 18ºC)
5-2 Setting the Process Water Temperature
To change the process water temperature set point:
• Press the
Up Arrow button to raise the set point.
• Press the
Down Arrow button to lower the set point.
5-3 LED
Indicators
PV or Process Value Numeric LED
During normal operation, the large red
PV
LED on the controller displays the actual
process temperature at the To Process thermocouple. It also lists parameter symbols
during setup and error messages if an error occurs.
SV or Set Value Numeric LED
During normal operation, the green
SV
LED on the controller displays the process set
point you want the chiller to maintain. It also displays parameter and pre-set function
values during setup.
OUT1 LED
The orange
OUT1
LED lights when the control output energizes the hot-gas bypass
solenoid valve.