beautypg.com

Specifications and technical data – Soleus Air KFHHP-18-ID User Manual

Page 6

background image

- 4 -




Specifications and Technical Data

Model

KFHHP-18-ID / KFHHP-18-OD

Function

Heating and Cooling

Cooling capacity(BTU/hr) & (Watts)

18000 / 5300 (1400-6000)

Heating capacity(BTU/hr) & (Watts)

20000 / 6000 (1100-7000)

Rated voltage

208-230V~

Rated Frequency

60Hz

Cooling/Heating rated current(A)

10.6/10.6

Cooling/Heating rated power(W)

2440/2440

Cooling/Heating power input(W)

1350/1800

SEER 13.25

EER/COP(W/W) 3.93/3.22

HSPF 8.5

Recycling Air Volume(m

3

/h)

800

Factory Charge 410A (lbs.)*

R410A 3.9 lbs

Noise (Indoor/Outdoor) dBA

50/57

Maximum Vertical

16.4 ft

Height Differential

Maximum Length

32.8 ft

Net Weight (Indoor/Outdoor) (lb)

28.7/130.1

Dimensions (Indoor/Outdoor)
(WxDxH)(inch)

Indoor unit :40.16” Ч 8.98” Ч12.20”

Outdoor unit:37.40” Ч 13.39” Ч 26.93”

Connection Pipe:

Length (ft)

26.25

Gas additional charge(oz/ft)

0.21

Liquid Pipe (mm)

Φ

9.52(5/8”)

Outer Diameter

Gas Pipe (mm)

Φ

16(3/8”)

Height (ft)

26.25

Max Distance

Length (ft)

49.21

™ All above are tested and certified to ETL specification. Among them, the cooling capacity, heating

capacity and noise level are tested before shipment.

™ In case of any change in performance parameters, the data provided on nameplate shall prevail.

™

Test the maximum input power under maximum cooling condition (89.6°F /73.4°F, 109.4°F /78.8°F)
and maximum heating condition (44.6°F /-, 75.2°F /69.8°F).

™ Working temperature range

Indoor side DB/WB(°F)

Outdoor side DB/WB(°F)

Maximum cooling

89.6 / 73.4

109.4 / 78.8(T1)

Minimum cooling

69.8 / 59

64.4 / -

Maximum heating

80.6 / -

75.2 / 64.4

Minimum heating

68 / -

19.4 / 17.6

This manual is related to the following products: